Fault Messages - Viessmann Vitotwin 300-W Installation And Service Instructions For Contractors

Micro chp boiler based on stirling engine natural gas version
Hide thumbs Also See for Vitotwin 300-W:
Table of Contents

Advertisement

Fault messages

Explanatory notes on resetting (see
table below)
AR
Automatic restart after the fault
has been remedied
ARP Automatic restart after the fault
has been remedied and mains
voltage disconnected
Fault mes-
Cause
sage
"10: Outside
Short circuit or lead break to
sensor"
outside temperature sensor.
"20: Boiler
Short circuit or lead break to
sensor 1"
boiler temperature sensor.
"30: Flow
Short circuit or lead break to
sensor 1"
flow temperature sensor,
heating circuit 1.
"32: Flow
Short circuit or lead break to
sensor 2"
flow temperature sensor,
heating circuit 2.
"40: Return
Short circuit or lead break to
sensor 1"
return temperature sensor.
"50: DHW
Short circuit or lead break to
sensor 1"
cylinder temperature sensor
B3.
"60: Room
Short circuit or lead break to
sensor 1"
room thermostat, heating cir-
cuit 1.
"65: Room
Short circuit or lead break to
sensor 2"
room temperature sensor,
heating circuit 2.
"68: Room
Short circuit or lead break to
sensor 3"
room temperature sensor,
heating circuit 3.
"70: Buffer
Short circuit or lead break to
sensor 1"
buffer temperature sensor.
"71: Buffer
sensor 2"
"72: Buffer
sensor 3"
UR
Press
SR
Service reset (see page 122)
NRP No restart possible, replace PCB
Remedy
Check outside temperature
sensor (see page 139)
Check the boiler water tem-
perature sensor (see
page 141)
Check flow temperature sen-
sor (see page 146)
Check the return tempera-
ture sensor (see page 143)
Check the cylinder tempera-
ture sensor (see page 140)
Check room thermostat and
connecting cable.
Check buffer temperature
sensor (see page 140)
Troubleshooting