Viessmann Vitotwin 300-W Installation And Service Instructions For Contractors page 125

Micro chp boiler based on stirling engine natural gas version
Hide thumbs Also See for Vitotwin 300-W:
Table of Contents

Advertisement

Fault messages
Fault mes-
Cause
sage
"121: Flow
Set flow temperature for
temp HC1"
heating circuit 1 not reached
"122: Flow
Set flow temperature for
temp HC2"
heating circuit 2 not reached
"127: Le-
Higher DHW temperature not
gionella
reached
temp"
"157: Boiler
Temperature limiter in the
flow thermo-
safety chain has tripped.
stat"
"158: Con-
Level switch has tripped.
densate"
(cont.)
Remedy
Check flow temperature sen-
sor and lead (see page 146).
Check that the flow tempera-
ture sensor is installed cor-
rectly.
Check temperature sensors
(see page 140).
Check the system pressure.
Vent the heating system.
Check whether there is any
throughput (code 8366 in di-
agnostics heat generation)
Check function of 3-way
diverter valve.
Check the system pressure.
Vent the heating system.
Check whether there is any
throughput (code 8366 in di-
agnostics heat generation)
Check function of the circula-
tion pump.
Check function of 3-way
diverter valve.
Check condensate drain,
clean siphon.
Check installation position
and function of the level
switch.
Troubleshooting