Viessmann Vitotwin 300-W Installation And Service Instructions For Contractors page 99

Micro chp boiler based on stirling engine natural gas version
Hide thumbs Also See for Vitotwin 300-W:
Table of Contents

Advertisement

Changing codes
"Heating circuit 3"
Function
"Room temperature
comfort setpoint"
"Room temperature re-
duced setpoint"
"Room temperature frost
protection setpoint"
"Heating curve slope"
(see page 81)
"Heating curve displace-
ment" (see page 81)
"Summer/winter heating
limit" (see page 159)
"24-hour heating limit"
(see page 159)
"Flow temp setpoint
min"
"Flow temp setpoint
max"
"Room temperature in-
fluencing factor"
"Type room controller"
(see page 160)
"Room temp limitation"
(cont.)
Code
Operat-
ing level
1310
"E"
1312
"E"
1314
"E"
1320
"F1"
1321
"F1"
1330
"F1"
1332
"F2"
1340
"F2"
1341
"F2"
1350
"F2"
1359
"F2"
1360
"F2"
Setting options
Delivered
condition
6 to 35 °C
20.0
6 to 35 °C
14.0
4 to 35 °C
4.0
0.10 to 4.00
1.40
- 4.5 to 4.5 °C
0.0
- - -/8 to 30 °C
18
- - -/- 10 to 10 °C
0
8 to 95 °C
20
8 to 95 °C
80
- - -/0 to 100 %
0
■ "Manually"
"Radiator
■ "Radiator
medium"
fast"
■ "Radiator me-
dium"
■ "Radiator
slow"
■ "Floor heat
fast"
■ "Floor heat
medium"
■ "Floor heat
slow"
- - -/0.5 to 4.0 °C
2.0
Codes
99

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

C3ha

Table of Contents