Troubleshooting

Fault Messages

Displayed
System characteristics
fault code
F.5
System continues op-
erating in normal mode
with replacement value.
F.7
No DHW heating
F.8
No DHW heating
F.13
Regulates as if the out-
side temperature were
32°F (0°C).
F.14
Regulates as if the out-
side temperature were
32°F (0°C).
F.49
Burner in a fault state
F.50
Burner in a fault state
F.59
Burner locked out
72
Vitodens 100-W, B1HE/B1KE Combi Installation/Service
Note: For diagnostics and troubleshooting, see chapter
Cause
Measures
Lead break or short
Check plug 33/X6 and cable:
circuit
pin 1 and 2.
off and back on again.
Lead break, storage
tank temperature
sensor
Short circuit, storage
Check storage tank temperature sensor (plug 5, wires
tank temperature
3 and 4).
sensor
Replace faulty component if necessary.
Lead break, outside
temperature sensor
Replace faulty component if necessary.
Short circuit, out-
Check outside temperature sensor and connection to
side temperature
sensor (external plug, and contacts 1 and 2).
sensor
Replace faulty components if necessary.
Flue gas temperature
Check flue gas temperature sensor.
sensor disconnection
Reset the boiler.
Short circuit, flue gas
Check flue gas temperature sensor.
temperature sensor
Reset the boiler.
Power supply, low
Check mains voltage.
voltage
If voltage is correct and the fault occurs repeatedly,
replace the fan unit.
"Repairs".
Fault messages dependent on boiler equipment
level
Check voltage level, to see if 5V present at plug 33,
Turn the gas condensing system boiler ON/OFF switch
Check DHW setting in the commissioning
assistant and correct if necessary.
Check storage tank temperature sensor (plug 5,
wires 3 and 4).
Measure voltage at sensor input on electronics
module. Target value: 3.3V– with sensor disconnected.
Replace faulty component if necessary.
Check the operating mode setting in the
commissioning assistant and correct if necessary.
Check outside temperature sensor and connection to
sensor (external plug, contacts 1 and 2).
Measure voltage at sensor input on electronics module.
Target value: 3.3V– with sensor disconnected.