Siemens SMART 7KT Operating Instructions Manual page 5

Hide thumbs Also See for SMART 7KT:
Table of Contents

Advertisement

Confi guration
There are 4 dedicated keys labelled as F1, F2, F3, F4. Use
these 4 keys to read meter parameters. Simply press these
keys to read the parameters.
KEY
ONLINE PAGE DESCRIPTION
PRESS
Press
The fi rst screen: Displays line to neutral voltage of three phase
"F1"
and average line to neutral voltage.
The second screen: Displays line to line voltage of three phase
and average line to line voltage.
The third screen: Displays total percentage harmonics of line
to neutral voltage of three phase and average line to neutral
voltage.
The fourth screen: Displays total percentage harmonics of line
to line voltage of three phase and average line to line voltage.
Note: 1) For 3 Ø 3 wire system, only second and fourth
screens will be available.
2) For 1 Ø 2 wire system, only fi rst and third screens will
be available.
The fi fth screen: Displays phase current of three phase and
neutral current.
The sixth screen: Displays phase maximum current demand of
three phase and average current.
The seventh screen: Displays total percentage harmonic of
current of three phase and average phase current.
Note: 1) For 3 Ø 3 wire system only fi fth, sixth and seventh
screen will be available. Displays average current
instead of neutral current.
2) For 1 Ø 2 wire instead only fi fth sixth and seventh
screen will be available.
Press
The fi rst screen: Displays voltage, current, power factor of fi rst
"F2"
phase and frequency.
The second screen: Displays voltage, current, power factor of
second phase and frequency.
The third screen: Displays voltage, current, power factor of
third phase and frequency.
The fourth screen: Displays average value of voltage, current
and power factor of three phase and frequency.
Note: 1) For 3 Ø 3 wire system voltage, current, power factor
and frequency will be line to line.
2) For 1 Ø 2 wire system only fi rst screen will be
available.
Press
The fi rst screen: Displays power factor of three phase and
"F3"
average power factor.
The second screen: Displays phase angle of three phase and
Average angle
Note: 1) For 3 ø 3 wire system, only average power factor and
average angle will be available on this screen.
The third screen: Displays active power of three phase and
total active power.
The fourth screen: Displays reactive power of three phase and
total reactive power.
The fi fth screen: Displays apparent power of three phase and
total apparent power.
The sixth screen: Displays active, reactive, apparent power and
power factor of fi rst phase.
The seventh screen: Displays active, reactive, apparent power
and power factor of second phase.
The eighth screen: Displays active, reactive, apparent power
and power factor of third phase.
The ninth screen: Displays total active, reactive, apparent
power and average power factor of three phase.
The tenth screen: Displays maximum active power demand,
reactive power demand and apparent power demand.
The eleventh screen: Displays minimum active power demand
and reactive power demand.
Note: 1) For 3 Ø 3 wire system only ninth, tenth and eleventh
screen will be available.
2) In1Ø 2 wire system only fi rst, second, third, fourth,
fi fth, sixth, ninth, tenth, eleventh screen will be
display
KEY
ONLINE PAGE DESCRIPTION
PRESS
Press
The fi rst screen: Displays import active energy of fi rst phase.
"F4"
The second screen: Displays import active energy of second
phase.
The third screen: Displays import active energy of third phase.
The fourth screen: Displays export active energy of fi rst phase.
The fi fth screen: Displays export active energy of second
phase.
The sixth screen: Displays export active energy of third phase.
The seventh screen: Displays total import active energy of
three phase.
The eighth screen: Displays total export active energy of three
phase.
The ninth screen: Displays total net active energy of three
phase.
The tenth Screen: Displays import reactive energy of fi rst
phase.
The eleventh screen: Displays import reactive energy of
second phase.
The twelfth screen: Displays import reactive energy of third
phase.
The thirteenth screen: Displays export reactive energy of fi rst
phase.
The fourteenth screen: Displays export reactive energy of
second phase.
The fi fteenth screen: Displays export reactive energy of third
phase.
The sixteenth screen: Displays total import reactive energy of
three phase.
The seventeenth screen: Displays total export reactive energy
of three phase.
The eighteenth screen: Displays total net reactive energy of
three phase.
The nineteenth screen: Displays apparent energy of fi rst
phase.
The twentieth screen: Displays apparent energy of second
phase.
The twenty fi rst screen: Displays apparent energy of third
phase.
The twenty second screen: Displays total net apparent energy
of three phase.
The twenty third screen: Displays ON hour.
Note: 1) In 3 Ø 3 wire system only seventh, eighth, ninth,
sixteenth, seventeenth, eighteenth, twenty second
and twenty third screens will be available.
2) In 1Ø 2 wire system fi rst, fourth, seventh, eighth,
ninth, tenth, thirteenth, sixteenth, seventeenth,
eighteenth, nineteenth, twenty second and twenty
third screens will be available.
AUTOMATIC / MANUAL MODE DESCRIPTION
Press F4 key for 3 seconds to toggle between Automatic and Manual
mode.
Note: By default unit operates in automatic mode.
In automatic mode online pages scroll automatically at the rate of 5
seconds per page.
In automatic mode when any key is pressed, unit temporarily switches
to manual mode and the appropriate page is displayed, also if any key
is not pressed for 5 sec, unit resumes automatic mode.
SERIAL NUMBER DESCRIPTION
Press F3 key for 5 sec. to display 8 digit serial number only for 5 sec. at
5th line of display
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

7kt0310

Table of Contents