background scanning is mandatory if there are more than one NETA-21 accessing
more than six Ethernet-connected control units at a time.
6. After you save the settings for ETH1 interface, use the available port in the fieldbus
adapter module and connect the ACS880 drive to NETA-21. See below figure.
Computer
Ethernet port
7. Add the configured fieldbus adapter module's IP address to Ethernet devices list. To
add, click Add button and enter the IP address.
8. Click Create device.
Note: When you configure multiple devices in the same NETA-21, make sure that you
use a different subnet for the Ethernet network that is used for ACS880 drives and the
cellular router connection. Usage of same subnet can cause issues in detecting the
ACS880 device. Change the subnet and IP address of each drive accordingly in the
fieldbus adapter module's Ethernet port settings. Se parameter group 51 FBA A
settings.
Connecting multiple ACS880 devices to NETA -21
To connect multiple ACS880 devices to NETA -21 through Ethernet, use a hub or
switch. Configure all the drives to be on the same subnet, connect all of them to the
Network and drive connectivity configuration 41
ACX580/
ACS880
Drive
(option slot
1 or 2)
Fieldbus
adapter
module
X1
X2
ABB Ability
NETA-21
ETH1
ETH2