8.10.1 Checking and, if required, adjusting the gas/air ratio

▶ Switch off the appliance.
▶ Remove the front cover.
▶ Remove the combustion cover.
Fig. 100 Removing the combustion cover
1
Fig. 101 Setting the adjustable venturi
[1]
Security Seal
[2]
Adjustable venturi
▶ Switch on the appliance.
▶ Remove the plug from the flue gas test port.
▶ Push the flue gas probe centrally into the flue gas test port.
Greenstar 8000 Life – 6720883865 (2021/11)
2.
1.
0010020558-002
2
0 010 020 540-002
▶ Seal the test point.
Fig. 102 Flue gas test port
▶ To ensure heat transfer: open the radiator valves.
▶ Set the chimney sweep mode and start up the appliance at maximum
rated output.
▶ Measure the CO
or O
content.
2
2
▶ Check the CO
or O
content at maximum rated output according to
2
2
Tab. 29 and adjust if required.
Security Seal [1] ( Fig. 101) must be removed before adjusting the
Max CO
setting. Once adjustment has been made the seal must be
2
replaced with part number 8737708988.
▶ To increase the CO
content, remove seal [1] and turn the adjustable
2
venturi to the left.
▶ To reduce the CO
content, remove seal [1] and turn the adjustable
2
venturi to the right.
Maximum rated output
Gas type
CO
O
2
2
Natural gas
9.5%
4.0% <250ppm 8.6%
± 0.4
Liquid
10.8%
4.6% <250ppm 10.2%
propane (LPG)
± 0.4
Table 29 CO
and O
contents
2
2
▶ Measure the CO content.
The CO content must be < 250ppm.
▶ Set the minimum rated output.
▶ Measure the CO
or O
content.
2
2
Inspection and maintenance
0010023633-001
Minimum rated output
CO
CO
O
CO
2
2
5.5% <75ppm
± 0.4
5.5% <75ppm
± 0.4
69