Bradford White Brute MagnaTech BMGV1600 Installation And Operation Instructions Manual page 98

Hide thumbs Also See for Brute MagnaTech BMGV1600:
Table of Contents

Advertisement

Page 94
224
Invalid DHW (Domestic Hot Water)
demand source setting
225
Invalid Flame threshold setting
226
Invalid Outlet high limit setpoint setting
227
Invalid DHW (Domestic Hot Water) high
limit setpoint setting
228
Invalid Stack limit setpoint setting
229
Invalid Modulation output setting
230
Invalid CH (Central Heat) demand
source setting
231
Invalid Delta T limit delay setting
232
Invalid Pressure sensor type setting
234
Invalid Outlet high limit enable setting
235
Invalid Outlet connector type setting
236
Invalid Inlet connector type setting
237
Invalid DHW (Domestic Hot Water)
connector type setting
238
Invalid Stack connector type setting
239
Invalid Header connector type setting
240
Invalid Outdoor connector type setting
L
L
L
L
L
selected parameters, reverify and reset module.
L
2. If fault repeats, verify electrical grounding.
L
3. If fault repeats, replace module.
L
L
L
L
L
L
L
L
L

Advertisement

Table of Contents
loading

Table of Contents