9.11 Combustion Setup Procedure

In this section, we will explain how to set up the gas
Fire and Low Fire conditions.
Required tools: Screwdrivers, Torx bits, Allen
Wrench Set, Combustion Analyzer
WARNING
Improper adjustment may lead to poor combustion
quality, increasing the amount of carbon monoxide
produced. Excess carbon monoxide levels may
lead to personal injury or death.
1.
On the Main Gas Valve, locate the
offset.
Refer to Table 23 for appropriate CO2 ranges.
2.
Press the Control Icon at the center of the
Home Screen.
Menu 26. 'Home' screen
3.
The system will present the Status Summary
screen.
Menu 27.
Status Summary Screen
corner.
Menu 28.
"Burner Control Ignition."
Menu 29. Burner Control Ignition
Once there select "Pilot Test Hold" and turn
this feature "ON." This feature will allow
the pilot to stay lit for setup and will NEVER
heat and the boiler will begin its sequence of
operation (Refer to Section 12.8 for sequence
of operation, and Table 22 for required pilot
valve pressures.)
6.
Once the pilot has lit, adjust pilot regulator
pressure to that described in Table 22.
glass. An adjustment to the pilot regulator
Use the regulator adjustment to adjust pilot
the pressure in the pilot valve (See Table 22).
7.
Once the desired pilot has been established,
turn the call for heat OFF and return to "Burner
Page 75