Parameter Defaults and Ranges (continued)
Lead Lag Master Config-
Adv Settings - Outdoor Reset
Lead Lag Master Config-
Adv Settings - Outdoor Reset
Lead Lag Master Config-
Adv Settings - Outdoor Reset
Lead Lag Master Config-
Adv Settings - Outdoor Reset
Lead Lag Master Config-
Adv Settings - Outdoor Reset
Lead Lag Master Config-
Adv Settings - Outdoor Reset
Lead Lag Master Config-
Adv Settings - Outdoor Reset
Lead Lag Master Config-
Adv Settings - Outdoor Reset
Lead Lag Master Config-
Adv Settings-Add Stage
Lead Lag Master Config-
Adv Settings-Add Stage
Lead Lag Master Config-
Adv Settings-Add Stage
Lead Lag Master Config-
Adv Settings-Add Stage
Lead Lag Master Config-
Adv Settings-Add Stage
Lead Lag Master Config-
Adv Settings-Drop Stage
Lead Lag Master Config-
Adv Settings-Drop Stage
Lead Lag Master Config-
Adv Settings-Drop Stage
Lead Lag Master Config-
Adv Settings-Drop Stage
Lead Lag Master Config-
Adv Settings-Drop Stage
Lead Lag Master Config-
Adv Settings-Drop Stage
Lead Lag Master Config-
Adv Settings-Drop Stage
Lead Lag Master Config-
Adv Settings-Modulation
Lead Lag Master Config-
Adv Settings-Modulation
Lead Lag Master Config-
Adv Settings-Modulation
Lead Lag Master Config-
Adv Settings-Modulation
Lead Lag Master Config-
Adv Settings-Modulation
Parameter and Range Table (cont)
Enable
Maximum Outdoor Temperature
Minimum Outdoor Temperature
Low Water Temperature
Minimum Boiler Water Temp
Outdoor Boost Time
Outdoor Boost Step
Outdoor Boost Maximum Off Point
Method 1
Detection Time 1
Error Threshold
Rate Offset
Interstage Delay
Method 1
Detection Time 1
Error Threshold
Rate Offset
Interstage Delay
Boiler Off Option
All Boilers Off Threshold
Off Hysteresis
On Hysteresis
P Gain
I Gain
D Gain
Enable
Disable
40F - 150F
-40F - 90F
40F - 160F
40F - 190F
15 min 0 sec - 600 min 0 sec
0F - 50F
40F - 200F
Error Threshold
Firing Rate Threshold
Disable
0 min 15 sec - 240 min 0 sec
0F - 50F
0% - 100%
0 min 0 sec - 120 min 0 sec
Error Threshold
Firing Rate Threshold
Disable
0 min 0 sec - 15 min 0 sec
0F - 50F
0% - 100%
0 min 0 sec - 15 min 0 sec
All Boilers Off
Drop Lead Boiler on Error Threshold
50F - 210F
0F - 30F
2F - 30F
0-100
0-100
0-100
Disabled
65F
40F
120F
120F
240 min or (4 Hrs)
0F
200F
Error Threshold
0 min 15 sec
5F
20%
5 min 0 sec
Error Threshold
0 min 2 sec
2F
20%
0 min 2 sec
Disabled
210F
10F
5F
20
10
0