Section 1
GENERAL INFORMATION
1.1

Introduction

This manual includes information which will help you to
install, operate, and maintain the 1600, 2000, 2500, 3000,
3500 and 4000 MBH systems. Please read this manual
completely before proceeding with the installation. If
you have any questions regarding this equipment, please
consult the manufacturer, or a local manufacturer's
representative. Many operating problems are caused by
improper installation.
Primary information regarding your unit can be found
on the Rating Plate which is on the outside face of the
right-side panel.
1.2

Safety Notes

DANGER
• Water temperature over 125°F (52°C) can cause
severe burns instantly or death from scalds.
• Children, disabled and elderly are at highest risk of
being scalded.
• See instruction manual before
setting temperature at
heating appliance.
• Feel water before
bathing or showering.
• If this appliance is used
to produce water that
could scald if too hot,
such as domestic hot water
use, adjust the outlet
control (limit) or use temperature limiting valves to
obtain a maximum water temperature of 125°F (52°C).
WARNING
Fire or Explosion Hazard
Improper configuration can cause fuel buildup and
explosion. Improper user operation may result in
property loss, severe physical injury, or death.
Any changes to safety-related configuration parameters
must only be done by experienced and/or licensed
burner/boiler operators and mechanics.
If any odor of gas is detected, or if the gas burner does
not appear to be functioning in a normal manner, close
the main gas shutoff valve. Do not shut off the power
switch. Contact your heating contractor, gas company,
or factory representative.
The unit is protected against over-pressurization. A
pressure relief valve is included with each unit.
The inlet gas pressure to the appliance must not exceed 13"
W.C. (3.2 kPa).
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-Latest
Edition "National Fuel Gas Code" or
2) CSA B149.1 "Natural Gas and Propane Installation
Code" and with the requirement of the local utility or
other authorities having jurisdiction. Such applicable
requirements take precedence over the general instructions
contained herein.
WARNING
Carbon Monoxide Hazard
Improper adjustment of the burners may lead to poor
combustion quality, increasing the amount of carbon
monoxide produced. Excessive carbon monoxide levels
may lead to personal injury or death.