Advertisement

Model
Gas Type
Natural
1,600
Propane
Natural
2,000
Propane
Natural
2,500
Propane
Natural
3,000
Propane
Natural
3,500
Propane
Natural
4,000
Propane
* - Only check the pressures if there are problems getting the CO
Table 23. CO
Range and Pressure Differential
2
Gas Valve
Figure 45. High and Low Fire Adjustments on the Gas Valve
High Fire CO
Low Fire CO
2
9.0% ± 0.2
10.0% ± 0.2
9.0% ± 0.2
10.0% ± 0.2
9.0% ± 0.2
10.0% ± 0.2
9.0% ± 0.2
10.0% ± 0.2
9.0% ± 0.2
10.0% ± 0.2
9.0% ± 0.2
10.0% ± 0.2
Pressure Differential
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
0.9" to .09" wc
2
0.9" to .09" wc
2
0.5" to 1.2" wc
2
0.5" to 1.2" wc
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
0.5" to 1.2" wc*
2
and CO values in range.