3 Fix the cable with cable ties to the cable tie mountings.
7
Finishing the outdoor unit
installation
7.1
To check the insulation resistance
of the compressor
NOTICE
If, after installation, refrigerant accumulates in the
compressor, the insulation resistance over the poles can
drop, but if it is at least 1 MΩ, then the unit will not break
down.
▪ Use a 500 V mega-tester when measuring insulation.
▪ Do NOT use a mega-tester for low voltage circuits.
1 Measure the insulation resistance over the poles.
If
≥1 MΩ
Insulation resistance is OK. This procedure is
finished.
<1 MΩ
Insulation resistance is not OK. Go to the next step.
2 Turn ON the power and leave it on for 6 hours.
Result: The compressor will heat up and evaporate any
refrigerant in the compressor.
3 Measure the insulation resistance again.
8

Configuration

INFORMATION
Heating is only applicable in case of reversible models.
8.1

Overview: Configuration

This chapter describes what you have to do and know to configure
the system after it is installed.
NOTICE
This chapter explains only the basic configuration. For
more detailed explanation and background information,
see the installer reference guide.
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688014-1D – 2022.10
14a
X2M
Then

7 Finishing the outdoor unit installation

Why
If you do NOT configure the system correctly, it might NOT work as
expected. The configuration influences the following:
▪ The calculations of the software
▪ What you can see on and do with the user interface
How
You can configure the system via the user interface.
▪ First time – Configuration wizard. When you turn ON the user
interface for the first time (via the unit), the configuration wizard
starts to help you configure the system.
▪ Restart the configuration wizard. If the system is already
configured, you can restart the configuration wizard. To restart the
configuration
wizard,
go
Configuration wizard. To access Installer settings, see
"8.1.1 To access the most used
▪ Afterwards. If necessary, you can make changes to the
configuration in the menu structure or the overview settings.
INFORMATION
When the configuration wizard is finished, the user
interface will show an overview screen and request to
confirm. When confirmed, the system will restart and the
home screen will be displayed.
Accessing settings – Legend for tables
You can access the installer settings using two different methods.
However, NOT all settings are accessible via both methods. If so,
the corresponding table columns in this chapter are set to N/A (not
applicable).
Method
Accessing settings via the breadcrumb in the
home menu screen or the menu structure.
To enable breadcrumbs, press the
in the home screen.
Accessing settings via the code in the
overview field settings.
See also:
settings" [ 4  28]
"To access the installer
"8.5 Menu structure: Overview installer
8.1.1

To access the most used commands

To change the user permission level
You can change the user permission level as follows:
1 Go to [B]: User profile.
B
User profile
2 Enter the applicable pin code for the user permission
level.
▪ Browse through the list of digits and change the
selected digit.
▪ Move the cursor from left to right.
▪ Confirm the pin code and proceed.
Installer pin code
The Installer pin code is 5678. Additional menu items and
installer settings are now available.
to
Installer
settings
commands" [ 4  27].
Column in tables
#
For example: [2.9]
button
Code
For example: [C-07]
settings" [ 4  34]
Installation manual
27
>