A circuit breaker of type B or C, of suitable current rating should be fitted.
A Residual Current Device (RCD) of suitable current rating should be fitted.
A short time delay AC-DC sensitive RCD is recommended.
The OE8013 requires a min 30mA trip level RCD.
The OE8014 requires a min 100mA trip level RCD.
Keep means of electrical isolation accessible at all times.
We recommend that the units are fitted to pedestals, as this gives optimal air flow
for cooling the units. Do not block or restrict the inlet filters on the appliance base.
Restricted airflow will result in reduced performance.
If the unit is not being fitted to a pedestal then fit the supplied air deflector as
illustrated, using the back panel screws:
HELD BY BACK PANEL
SCREWS
If the OE8013 is fitted to Floorstand OA8934 or Pedestal OA8970, then the supplied
stability bracket must be fitted for safety reasons.
IS 614 ECN 3862
REAR VIEW
32860 (OE8013)
32861 (OE8014)
AIR DEFLECTOR STRIP