Wiring Diagram

AC Hot or DC+
12/24VAC or 12/24VDC
AC Neu or DC-
Wire Sizing Chart
MAX distance between
Actuator and Supply (feet)
P1.A
Actuator/
Voltage
12VAC/DC
Amps
1.5A
Wire
Gage
18
55
16
87
14
140
The default settings in the controller are as follows:
P1.A
24VAC/DC
0.9A
Wire sizing data is provided in the Wire Sizing Data table to assist in the selection of
184
the proper wire size for ProMation P1.A series actuators using various wire sizes over
289
distance. Please make sure to reference the correct voltage and do not exceed the
indicated length of the wire run for each model.
466
Page 4 of 14 P1.A LV AdVanced Proportional Series
Proportional Control
BLK
WHT
1. Input/Output Signal:
2. Signal Response:
3. Loss of Signal:
4. Sensitivity Setting
4-20mA only
Direct Acting (max signal = CCW)
Fail in Position
3: Approximately 30 steps for 90°