Other Specifications - Carel pCO3 Technical Leaflet

Electronic controller
Hide thumbs Also See for pCO3:
Table of Contents

Advertisement

Relation between AWG and wire cross-section
AWG
Cross-section (mm
20
0.5
15
1.5
14
2.5
pLAN network/user terminal connection
type
transmission speed
terminal connector
pLAN network/graphic terminal/aria terminal connector
The maximum distance between the pCO and user terminal is shown in the following table.
cable type
telephone
AWG24 shielded cable
AWG20/22 shielded cable
The maximum distance between two pCO
Note:
• a maximum of one terminal (pCOT, pCOI, pGD0, pGD1) can be connected, or two terminals but without using
use the backlighting on display. One version of the pCO
network.
• the graphic terminal and aria terminal should be always powered with a separate power supply.
• the 21 Vdc present at +Vterm (J24) can be used to power an external terminal with a maximum input of 2
W. Only one terminal can be connected (for example PLD terminal or ARIA terminal) in addition to the one
connected to terminal J10.

Other specifications

storage conditions
operating conditions
index of protection
environmental pollution
class according to protection against electric shock
PTI of the insulating materials
period of stress across the insulating parts
type of action
type of disconnection or microswitching
category of resistance to heat and fire
immunity against voltage surges
ageing characteristics (operating hours)
no. of automatic operating cycles
software class and structure
category of immunity to voltage surges (CEI EN 61000-4-5) Category III
The device is not designed to be hand-held
WARNING
• for applications subject to strong vibrations (1.5 mm pk-pk 10/55 Hz), secure the cables connected to the µ
pCO
using clamps placed around 3 cm from the connectors
3
• If the product is installed in industrial environments (application of the EN 61000-6-2 standard) the length of
the output connections must be less than 30 m.
• installation must be performed according to the standards and legislation in force in the country where the
appliance is used;
• for safety reasons the appliance must be housed inside an electrical panel, so that the only accessible part is the
display and the control keypad;
• all the very low voltage connections (analogue and digital inputs at 24 Vac/Vdc, analogue outputs, serial bus
connections, power) must have reinforced or double insulation from the mains;
• in the event of malfunctions do not attempt to repair the appliance, but rather contact the REHAU service
centre;
• in domestic environments, the connection cable between the pCO
+05C003290 - 1.5 - 09.09.2008
) Current
2
2
6
8
power supply distance
50 m
200 m
500 m
controllers with AWG20/22 shielded cable is 500 m.
3
RS485 half-duplex asynchronous
62.5 Kbps or 115.2 Kbps, selectable via software
6 pin telephone (J10)
3 pin plug-in connector (J11)
power supply
taken from the pCO (150 mA)
taken from the pCO (150 mA)
separate power supply via TCONN6J000
features optically-isolated connection to the pLAN
3
-40T70 °C, 90% RH non-condensing
-25T70 °C, 90% RH non-condensing
IP20, IP40 front panel only
normal
to be incorporated into Class I and/or II appliances
250 V
long
1C
microswitching
category D (UL94 - V0)
category 1
80,000
100,000 (EN 60730-1); 30,000 (UL 873)
Class A
and the terminal must be shielded.
3
18

Advertisement

Table of Contents
loading

Table of Contents