Install Wall-Mounting Frame; Connect The Pipe Of Indoor Unit; Install Drain Hose; Outlet Pipe - Gree GWH12AAB-K3NNA1A Service Manual

Refrigerant r410a
Table of Contents

Advertisement

Service Manual
(3) Fix the wall-mounting frame on the wall with tapping screws
(ST4.2X25TA) and then check if the frame is firmly installed by
pulling the frame. If the plastic expansion particle is loose,
please drill another fixing hole nearby.

3. Install Wall-mounting Frame

(1) Choose the position of piping hole according to the direction
of outlet pipe. The position of piping hole should be a little
lower than the wall-mounted frame.(As show in Fig.1)
Wall
Mark in the middle of it
Space
to the
wall
above
150mm
Left
Φ55mm
Rear piping hole
(2) Open a piping hole with the diameter of Φ55mm on the
selected outlet pipe position.In order to drain smoothly, slant
the piping hole on the wall slightly downward to the outdoor
side with the gradient of 5-10°.(As show in Fig.2)
Indoor
°
5-10
Note:
(1) Pay attention to dust prevention and take relevant safety
measures when opening the hole.
(2) The plastic expansion particles are not provided and should
be bought locally.

4. Outlet Pipe

(1) The pipe can be led out in the direction of right, rear right,
left or rear left.(As show in Fig.3)
(2) When selecting leading out the pipe from left or right, please
cut off the corresponding hole on the bottom case.(As show in
Fig.4)
Fig.3
Left
Cut off
the hole
Installation and Maintenance
Level meter
Fig.1
Rear piping hole
Outdoor
Fig.2
Φ55mm
Rear left
Right
Right
Fig.4

5. Connect the Pipe of Indoor Unit

(1) Aim the pipe joint at the corresponding bellmouth.(As show
in Fig.5)
(2) Pretightening the union nut with hand.
(3) Adjust the torque force by referring to the following sheet.
Place the open-end wrench on the pipe joint and place the
torque wrench on the union nut. Tighten the union nut with
torque wrench.(As show in Fig.6)
(4) Wrap the indoor pipe and joint of connection pipe with
insulating pipe, and then wrap it with tape.(As show in Fig.7)
Wall
Space
to the
wall
above
150mm
Pipe joint
Right
Φ55mm
Refer to the following table for wrench moment of force:

6. Install Drain Hose

(1) Connect the drain hose to the outlet pipe of indoor unit.(As
show in Fig.8)
(2) Bind the joint with tape.(As show in Fig.9)
Fig.8
Note:
(1) Add insulating pipe in the indoor drain hose in order to
prevent condensation.
(2) The plastic expansion particles are not provided.
(As show in Fig.10)
Pipe
Union nut
Torque wrench
Fig.5
Indoor pipe
Insulating pipe
Tightening torque(N . m)
Hex nut diameter(mm)
Φ6
Φ9.52
Φ12
Φ16
Φ19
Outlet pipe
Tape
Drain hose
Outlet
pipe
Drain hose
Insulating pipe
Open-end
wrench
Union nut
Pipe
Fig.6
Fig.7
15~20
30~40
45~55
60~65
70~75
Drain hose
Fig.9
Fig.10
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents