Configuration

Program the 'debounce' option and value using the following instruction:
#[PIN][space]<object>:<item>=<value>[dot]
#12345 site:debounce=value. (e.g #12345 site:debounce=1min)
The value must be written in the following format "0 sec", "5 secs", "10 secs", "30 secs", "1 min", "5
mins", "10 mins", "15 mins"
For example:
#12345 site:debounce=10 secs.

Clearing the configuration settings

To clear all of the SMS Lite configuration settings, use the message:
#[PIN][space]Defaults[dot]
Note: This command will also clear all the programmed telephone numbers

Supply Voltage Alarm

If the SMS Lite supply voltage drops below 10.5V DC, Ph1 will receive this notification message:
The supply voltage at <site> has gone low.
When the voltage increases above 11.5V DC a supply voltage message will be sent:
The supply voltage at <site> has returned to normal.
Supply voltage alarms do not escalate like input alarms. Supply voltage can be queried at any time using the

Operational Commands

Inputs

To acknowledge an alarm:
OK <input name> (e.g. Text: OK Pump)
This will stop any further escalation of the alarm to the numbers in the phone list for that input
status change. It will begin at the top of the list the next time the input is activated.
To force the SMS Lite to send the alarm message to the next phone number in the list.
BUSY <input name> (e.g. Text: BUSY Pump)
Not available to the last phone number in the list of that input.
Alarm message for one person:
<Site> <Input> has turned ON. (e.g. Text: Shed1 Pump has turned ON)
SMS Lite 4G– User Guide
STATUS command
© 2021 QTech Data Systems Ltd