Appendix A. Flow Diagrams and Wiring Diagrams
RUN EQUIPMENT IN
NORMAL COOLING
MODE
RUN EQUIPMENT IN
NORMAL HEATING
MODE
DEACTIVATE ALL
EQUIPMENT
Figure 15. ComfortSense
LEGEND
HBSP − High Balance Set Point
LBSP − Low Balance Set Point
ODT − Outdoor Temperature
NOTES
LBSP and HBSP must not be set closer than 2ºF
2nd stage lock in temperature −20ºF to 75ºF (OFF)
Temperature
Heat Pump Heat Only
HBSP
Heat Pump or Gas/Oil Heat
LBSP
Gas/Oil Heat Only
ODT
< LBSP − 3
YES
?
NO
ODT
< LBSP − 3
?
YES
NO
De−energize
Y1 or Y1&Y2,
and G
506230−01 05/09
START
there a cooling
YES
demand
NO
there a heating
YES
demand
NO
there a
dehumidification
NO
demand
YES
EITHER true:
ONE OR
outdoor temp. > 95ºF;
BOTH TRUE
indoor temp. < 65ºF
®
Model L7742U Thermostat Operation with Humiditrol
Operation
A
YES
YES
NO
NO
Upstage
2nd stage
timer expired
demand
?
?
ODT
YES
NO
< HBSP − 3 or
(if HBSP is
OFF)
?
YES
YES
NO
NO
Upstage
3rd stage
timer expired
demand
?
?
Figure 16. Dual Fuel Flowchart
HUMIDITROL
Is
?
Is
?
Humiditrol Comfort
Adjust setting is:
Is
?
Is
NEITHER
IS TRUE
?
demand (W1) or EM
YES
De−energize
Y1, Y2, G
Energize Y1, B,
Stg1
G and start
NO
upstage timer
YES
Indoor heat
demand
?
NO
YES
Indoor heat
demand
?
Page 22
RUN
Is indoor
MAX
YES
temperature > 2ºF
above heating set
point
?
NO
Is
indoor temp.
MID
greater than the heat
YES
setpoint plus the cool
setpoint divided by 2?
NO
Is indoor
YES
temp. > 2ºF below
cooling set point
MIN
?
NO
®
START
NO
Indoor heat
demand
?
YES
Gas/oil
heat (non−HP)
YES
heat demand
?
NO
ODT above
LBSP +3
NO
?
A
YES
Compress-
or speed 1 (Y1
2nd stg
W1
only) ?
HP (Y2) or
Gas (W1)
NO
?
Y2
ODT
> stg2 (Y2)
lock in temp
NO
?
YES
HP
Stg2
Energize Y1, Y2,
stage
B, G and start
demand
upstage timer
?
EDA Enabled
De−energize
W1 and W2
HEAT PUMP
LOCKOUT
Energize 1st
stage gas/oil heat
(W1) and start
upstage timer
Indoor heat
demand
NO
?
YES
Upstage timer
expired
YES
?
NO
4th
stage demand
or 2nd stage gas/oil
NO
demand (W2)
?
YES
Energize W2
YES
NO
Indoor heat
demand
?