System Test Modes; Temperature Offset - Lennox ComfortSense 7000 Series Programming And Application Manual

Hide thumbs Also See for ComfortSense 7000 Series:
Table of Contents

Advertisement

Options Tab Installer Settings
TEMPERATURE OFFSET default is 0°F. This setting
can be used to offset the displayed space temperature by
up to +/− 5°F. This offset also applies to the control temper-
ature. Scroll to TEMPERATURE OFFSET; press ENTER.
Use arrows to select a new offset. Press SAVE.

TEMPERATURE OFFSET

DEFAULT(O°F)
3°F
HUMIDITY OFFSET default is 0%. This can be used to
offset the displayed and controlled space relative humidity
(RH) by up to +/− 10% RH. Scroll to HUMIDITY OFFSET;
press ENTER. Use arrows to select a new offset. Press
SAVE.
HUMIDITY OFFSET
DEFAULT(O%)
2%
See separate section (Page 17) for details.
COMPRESSOR PROTECT default is ON; it may be
turned OFF, however, after one compressor cycle, it will re-
vert back to ON. If the system is running in compressor
protection, the home screen displays WAIT" only if there
is cooling or heating call for the compressor (Y1/Y2). If
compressor protection is running and there is a demand for
electric heating, the system waits for the compressor
protection timer to expire. Scroll to COMPRESSOR PRO-
TECT; press ENTER. Use up/down arrows to select OFF.
Press SAVE.
COMPRESSOR PROTECT
DEFAULT(ON)
OFF
SYSTEM TEST MODES After the thermostat has been
installed and set−up, the installer may run a system test
function (accessed through the installer settings menu), to
test all cooling, heating, Emergency Heating stages and
FAN outputs. Scroll to SYSTEM TEST MODES and press
ENTER; select TEST OUTPUTS and press ENTER.

SYSTEM TEST MODES

TEST OUTPUTS
(continued)
SCROLL arrows move through a list of all signals, Y1 ON,
Y1 OFF, Y2 ON, Y2 OFF, etc. With a signal displayed,
press ENTER to start the test, (e.g. Y1 ON selected, press
ENTER brings on Y1; Y1 OFF selected, press ENTER
shuts off Y1. CANCEL, pressed at anytime during tests will
return the previous screen and also disable any test and
puts the thermostat back into normal mode.
Risk of equipment damage.
Can cause compressor failure.
In dual fuel system applications, do not turn on heat
pump and furnace at the same time in system test
mode.
All HVAC components can be tested to confirm the signals
between thermostat and unit are being sent and were re-
ceived.
NOTES:
After 5 minutes without a test being initiated, the test
modes is disabled and system goes back to the normal
mode (i.e. HOME screen).
When in SYSTEM TEST MODE, the compressor mini-
mum off timer is bypassed.
TEST OUTPUTS
Page 13
NOTICE
OFF
Y1 ON
Y1 OFF
Y2 ON
Y2 OFF
W1 ON
W1 OFF
W2 ON
W2 OFF
FAN (G) ON
FAN (G) OFF
H ON
H OFF
D ON
D OFF
O ON (B OFF)
B ON (O OFF)
ComfortSenset Touch Screen Thermostat

Advertisement

Table of Contents
loading

Table of Contents