Type
Model name
Power supply
Available voltage range
Starting current
Airflow rate
Fan
Type × Q'ty
Motor output
Sound pressure level *1
Sound power level
Heat exchanger type
Type × Q'ty
Compressor
Motor output
Refrigerant
Refrigerant oil
Enclosure
Dimensions
Net
(H × W × D)
Gross
Net
Weight
Gross
Size
Method
Connection pipe
Pre-charge length
Max. length
Max. height difference
Operation range
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m.
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer's anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
Cooling
Heating
Cooling
Heating
Cooling
Heating
Dimensions (H × W × D)
Fin pitch
Rows × Stages
Pipe type
Type (Material)
Fin
Surface treatment
Type
Factory charge
Type
Amount
Material
Color
Liquid
Gas
Cooling
Heating
- 81 -
Inverter heat pump
AOYG45LBTA
A
15.7
6,750
3
m
/h
6,200
W
dB (A)
55
dB (A)
68
mm
Corrugate (Aluminum)
Hydrophilic coating (Blue fin)
W
g
3
cm
Approximate color of Munsell 10YR 7.5/1.0
mm
1,460 × 1,050 × 445
kg
mm (in)
m
°C
AOYG54LBTA
230 V ~ 50 Hz
198—264 V
20.2
6,750
6,850
Propeller × 2
100 × 2
55
57
69
71
1,260 × 900 × 36.4
1.3
2 × 60
Copper
Twin rotary × 1
2,100
R410A
3,350
POE (RB68)
800
Steel
Beige
1,290 × 900 × 330
86
95
Ø 9.52 (Ø 3/8)
Ø 15.88 (Ø 5/8)
Flare
20
50
30
-15 to 46
-15 to 24
2-1. Specifications