Fujitsu ARYG12LHTBP Design & Technical Manual page 74

Hide thumbs Also See for ARYG12LHTBP:
Table of Contents

Advertisement

5) Auto restart
Enables or disables automatic restart after a power interruption.
Function number
40
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or exter-
nal device.
6) Room temperature sensor switching
(Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function number
42
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
7) Cold air prevention
This setting is to disable the cold air prevention function during heating operation. When disabled,
the fan setting will always follow the setting on the remote controller. (Excluding defrost mode)
Function number
43
8) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number
44
9) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number
46
10-2. Function settings by using remote controller
Setting value
00
01
Setting value
00
01
Setting value
00
01
Setting value
00
01
02
03
Setting value
00
01
02
03
- 68 -
Setting description
Enable
Disable
Setting description
Indoor unit
Both
Setting description
Enable
Disable
Setting description
A
B
C
D
Setting description
Operation/Stop mode 1
(Setting prohibited)
Forced stop mode
Operation/Stop mode 2
Factory setting
Factory setting
Factory setting
Factory setting
Factory setting
10. Function settings