False Alarm Immunity - FGD FlameSpec UV-IR User Manual

Flame detector
Hide thumbs Also See for FlameSpec UV-IR:
Table of Contents

Advertisement

FlameSpec UV-IR User Manual
JP5
Kerosene
Methanol
Ethanol
Isopropanol
Polypropylene
Paper
Low Sensitivity
Fuel
N-Heptane
LPG
JP5
Methanol
B.2

False Alarm Immunity

The following table shows test results of false alarm immunity for detectors configured to "Extreme"
sensitivity. For each radiation source a distance is listed. This is the minimum tested distance, from which the
detectors did not alarm when exposed to the radiation source (either modulated or non-modulated).
False Stimuli only at Extreme Sensitivity
False Alarm Source
Sunlight, Direct, Reflected
Incandescent frosted glass light, 300W
Fluorescent, 70W (3x23.3W)
Electric arc
Arc welding
Radiation heater, 1850W
Quartz lamp (1000W) shielded
Quartz lamp (500W) non-shielded
Mercury vapor lamp 160Wx3
Car Exhausts
Projector led
Solenoid bell
Soldering iron
Electric Drill
www.acornfiresecurity.com
1 x 1 ft
36 (11)
1 x 1 ft
36 (11)
1 x 1 ft
30 (9)
1 x 1 ft
31 (9.5)
1 x 1 ft
36 (11)
1 x 1 ft
23 (7)
1 x 1 ft
23 (7)
Size
Distance Feet
(m)
1 x 1 ft
16 (5)
32-in Plume
13 (4)
1 x 1 ft
16 (5)
1 x 1 ft
10 (3)
www.acornfiresecurity.com
F110V0020.05
1.5
1.4
1.3
1.2
1.4
1.7
2.0
Average Response
Time (Seconds)
0.9
1.0
2.6
1.1
Maximum Distance in ft (m)
2 (0.5)
2 (0.5)
2 (0.5)
10 (3)
2 (0.5)
2 (0.5)
7 (2)
2 (0.5)
2 (0.5)
2 (0.5)
2 (0.5)
2 (0.5)
2 (0.5)