Introduction; Key Features - FGD FlameSpec UV-IR User Manual

Flame detector
Hide thumbs Also See for FlameSpec UV-IR:
Table of Contents

Advertisement

FlameSpec UV-IR User Manual

1. Introduction

The FlameSpec-UV-IR flame detector provides ultra-fast response, high performance and reliable detection
of a large variety of fires including hydrocarbon fires (visible and non-visible), as well as hydrogen fires (FLS-
UV-IR only).
The detector addresses slow growing fires as well as fast eruptions of fire using improved UV-IR technology.
The detector operates in all weather and light conditions. It will automatically record a fire event (1 min
pre/post alarm) using the internal data logger.
This manual covers two UV/IR detector models:
1. FLS-UV-IR: Hydrogen and hydrocarbons flame detection. Spectrum response of IR radiation in the
3.0-4.0 micron range
2. FLS-UV-IR-F: Hydrocarbon flame detection. Spectrum response of IR radiation in the 4.0-5.0 micron
range

1.1 Key Features

High immunity: To false alarm
Ultra-fast detection mode: Within 5 milliseconds for Hydrogen fireballs or explosions
High sensitivity: Up to 100 ft. (30m) for a 1ft2 (0.1m2) n-heptane pan fire
Built-in-Test (BIT) - Automatic and manual self-test of window cleanliness and the overall operation of the
detector.
Window heater to avoid condensation and icing.
Tilt mounting bracket can be connected either above or below the detector.
UV and IR warning levels - 0-20mA - current output warning when elevated UV or IR radiation is
detected.
www.acornfiresecurity.com
F110V0020.05
www.acornfiresecurity.com