• Airflow: Selectable between Off to Max in 50 CFM increments.
Default = Off, 500 CFM, Max = (odu_size in KBTU * 400/12)
NOTE: Selected airflow used during hydronic heating is a fixed value, it
does not vary.
• Blower On Delay: Selectable from 0 to 240 seconds. Default = 30
seconds
• Blower Off Delay: Selectable from 0 to 240 seconds. Default = 0
seconds
6.4. Check out
PROPERTY DAMAGE AND/OR PERSONAL INJURY
HAZARD
Failure to follow this warning could result in property damage, personal
injury or death.
Before running Check Out mode, make sure that all HVAC equipment is
properly installed. See the equipment installation instructions for details
and additional safety information.
Touch CHECKOUT to view the equipment installed in the system.
Perform checkout test to make sure each piece of equipment is operating
properly.