• System in Control: The system will decide which stage should be
running to satisfy the heating demand.
• High Heat: Temperature below which only the high stage of heating
will be energized.
• Only Low Heat: The system will only run in low stage heating.

6.3.4.2. Cooling Lockout

Outside temperature below which cooling will not be provided. After the
selection is made, touch SAVE.
• Cooling Lockout Temp: None, 45, 50 or 55 (°F). Default = None
NOTE: When simultaneous heating and cooling demand feature is on,
the cooling lockout shall be ignored.

6.3.4.3. Defrost Interval

Time interval at which defrost cycles can occur on a heat pump. AUTO
means the defrost interval is optimized by the outdoor control. After the
selection is made, touch SAVE.
• Set Defrost Interval: 30, 60, 90, 120 minutes or AUTO. Default =
AUTO
NOTE: See Heat Pump Installation Instructions for Defrost Timing
Interval when using AUTO Defrost.