Chapter 2

2.1 Electro-Static Discharge Warning

Important:
Please take full E.S.D. precautions if it is necessary at any time to come
into contact with any circuit boards, components or connectors.
Electrostatic discharge can damage the components used in the RamSan
and its interfaces.

2.2 Battery Warning

The internal battery in the RamSan-120 is charged with enough voltage to
power a fully loaded system for approximately seven minutes. However,
the battery may not be fully charged when you install your system.
Therefore, ensure that your battery is fully charged before you use the
system where there is risk of power failure.
As a precaution, replace the RamSan's battery every two years. To obtain
spare or new battery for your RamSan, contact Texas Memory Systems.

2.3 System Inspection

Texas Memory Systems ships the RamSan with a packing list. Ensure that
you have received all of the components listed.
1) Examine the external chassis for any damage that might have
occurred during shipping.
2) Ensure that the power supply is locked securely in place.
3) Inspect the interface plate for any screws that might have loosened
during shipping.
4) Inspect the front panel display for damage.
5) Report any meaningful damage to Texas Memory Systems.

2.4 Rack Mounting

The RamSan-120 series solid state disk is a 1U rack-mountable system.
Texas Memory Systems ships the system with the slides and equipment
needed to install it into a standard 19" rack.

2.5 Connecting the Fibre Channel Ports

After you have inspected the system and properly mounted it, either
connect the Fibre Channel ports on the RamSan to your server or to a
Fibre Channel switch.
RamSan-120 User's Manual
– Installation
- 6 -