Trusted TMR 24V DC/48V DC
Output Module - 40 Channel
PD-T8461 Issue 16
Product Description
Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021
Supersedes Publication ICSTT-RM451C-EN-P - January 2019
Original Instructions

Advertisement

Table of Contents
loading

Summary of Contents for Rockwell Automation Trusted TMR 24V DC

  • Page 1 Trusted TMR 24V DC/48V DC Output Module - 40 Channel PD-T8461 Issue 16 Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021 Supersedes Publication ICSTT-RM451C-EN-P - January 2019 Product Description Original Instructions...
  • Page 2 If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
  • Page 3: Table Of Contents

    Rack 6: DISCREP ................. 26 Rack 7: HKEEPING ................26 Rack 8: INFO ..................28 Sequence of Events Configuration ............29 Chapter 5 Operation Front Panel ....................31 Module Status LEDs ..................32 I/O Status Indicators .................. 33 Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 4 Field Wiring Faults ..................35 Module Faults ..................... 35 Companion Slot ..................36 SmartSlot ....................36 Cold Start ....................36 Transfer between Active and Standby Modules ........37 Chapter 7 Specifications Appendix A History of Changes Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 5: Preface Summary Of Changes

    This document is based on information available at the time of its publication, however, they are subject to change from time to time. The latest versions of the manuals are available at the Rockwell Automation Literature Library: rok.auto/literature. Trusted release This technical manual was updated for Trusted Release 4.0.
  • Page 6 Some of the Articles in the Knowledgebase require a TechConnect℠ Support Contract. For more information, go to Knowledgebase Document ID: IP622- TechConnect Support Contract - Access Level & Features. Tip: Sign in to your Rockwell Automation account to view Knowledgebase articles. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 7: Product Overview

    • Front Panel Module status LEDs indicate Module health and operational mode (Active, Standby, Educated). • TϋV Certified IEC 61508 SIL 3. • Outputs are powered in isolated groups of eight. Each such group is a Power Group (PG). Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 9: Description

    Inter-Module Bus (IMB) which provides power and allows communication with the TMR Processor. In addition, all Modules have a field interface that is used to connect to Module-specific signals in the field. All Modules are Triple Modular Redundant (TMR). Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 10 Figure 1: Module Architecture All High Integrity I/O Modules are made up of four sections: Host Interface Unit (HIU), the Field Interface Unit (FIU), the Field Termination Unit (FTU), and the Front Panel Unit (or FPU). Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 11: Field Interface Unit (Fiu)

    DC Digital Output Module, the FIU contains one stage of the output switch structure, and sigma-delta (ΣΔ) output circuit for each of the 40 field outputs. Two additional ΣΔ circuits provide optional monitoring of the external field I/O supply voltage. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 12: Host Interface Unit (Hiu)

    LED indicators for the Front Panel. For every type of Trusted I/O Module, the FPU contains the Slice Healthy, Active/Standby, the Educated LED indicators, and the Module removal switches. Additional bicolor LEDs provide status indication for the individual I/O signals. Serial data interfaces Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 13: Line Monitoring And Output States

    Data input from the IMB is stored in redundant error-correcting RAM on each slice portion of the HIU. Received data is voted on by each slice. All data transmissions include a confirmation response from the receiver. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 14: Sequence Of Events Characteristics

    FIU in the Module. Any single switch or entire slice failure is designed to leave two of the three fail-safe switch channels operational to power the load. Figure 3: Output Switch Structure Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 15 Switch 1 and Switch 2 are in the off state. Their “home” FIU. The home FIU, supplies an independent control signal for the “downstream” FIU FSS. For an unfaulted transistor. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 16: Switch Diagnostics

    To support safe operation, the Output Module is equipped with a series of switches that provide source power to a group of eight output channels, a Power Group. The output Module Group Fail-Safe Switch (GFSS) is intended Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 17 GFSS can still be de-energized by stopping the comms clock. If a slice fails, the watchdog on the HIU times out and resets the slice, this shuts down the FIU power supply and the associated GFSS control signal also de-energizes. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 19: Installation

    I/O cables suitable for use with the Trusted TMR 24/48V DC Digital Output Module are detailed in the following Product Descriptions. • Trusted I/O Companion Slot Cables Product Description, publication ICSTT-RM311 (PD-TC200) • Trusted I/O SmartSlot Cables Product Description, publication ICSTT- RM313 (PD-TC500) Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 20: Termination

    Chan 34 (+) Pwr Group 5 Rtn Pwr Group 5 (+) Pwr Group 5 Rtn Chan 39 (+) Pwr Group 5 (+) Chan 35 (+) Chan 40 (+) Pwr Group 5 (+) Chan 36 (+) Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 21: Trusted Module Polarisation/Keying

    Module before fitting. Figure 5: Module Polarization For Cables with Companion slot installations, both keying strips must be polarized. For this Module (T8461) remove keying pins 1, 5 and 7. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 23: Application

    HKEEPING Housekeeping Registers Integer INFO I/O Module Information Integer There are two OEM parameters that are included in the first rack (DO Board). These OEM parameters define the primary Module position; declaring the Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 24 Table 6 Rack 2: STATE bit Descriptions Channel Description Field output channel 1 state Field output channel 2 state Field output channel 40 state Table 7 Rack 2: State Output Descriptions Channel Description Channel fault Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 25: Rack 3: Ai

    The CI board returns the field loop current at the output. Table 9 Rack 4: CI Descriptions Channel Description Field output channel 1 current Field output channel 2 current Field output channel 40 current Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 26: Rack 5: Line_Flt

    ‘1’ when a discrepancy condition is detected on that output channel’s output state (rack 2). Rack 7: HKEEPING This table describes Rack 7: HKEEPING. Table 12 Rack 7: Housekeeping Descriptions Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 27 FIU Output Group 4 Field Supply Voltage -32768 32767 1/500V FIU Board Temperature, Output Group 4 -32768 32767 (Note: Temperature, °C = input value / 256) FIU Output Group 5 Field Supply Voltage -32768 32767 1/500V Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 28: Rack 8: Info

    Module is healthy. The Active and Standby Module Mode is an integer indicating the current operating mode of the associated Module. The value indicates the current internal operating mode of the Module. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 29: Sequence Of Events Configuration

    SOE Log. The SOE Log can be monitored and retrieved using the SOE and Process Historian Package running on the EWS. This software package is described in Trusted Sequence of Events and Process Historian Package Product Description, publication ICSTT-RM243 (PD-T8013). Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 31: Operation

    Module from the Chassis. Limit switches detect the open/closed position of the ejector levers. The ejector levers are normally latched closed when the Module is firmly seated into the Controller or Expander Chassis. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 32: Module Status Leds

    Module slices. It performs a 2oo3 vote on each data bit from the slices and sets the indicators accordingly. The Module status indicator modes and their meanings are described as follows: Table 16 Module Status LEDs Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 33: I/O Status Indicators

    Output is On. Green – flashing No Load, output open circuit. Field short circuit, output over current protection triggered and output channel is latched off. Red-flashing Channel fault, or no field supply voltage. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 34 Operation Tip: The LEDs indicating channel status may be configured to suit user requirements by implementing the procedure for configuring the System.INI file detailed in Trusted Toolset Suite Product Description, publication ICSTT-RM249 (PD-T8082). Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 35: Fault Finding And Maintenance Fault Reporting

    Module replacement activities depend on the type of spare Module configuration that is chosen when the system was configured and installed. The Module may be configured with a Dedicated Standby Slot or with a SmartSlot for a spare replacement Module. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 36: Companion Slot

    Educated LED becomes steady green and the Active LED becomes red flashing. Input Modules are now reading and reporting their inputs. Output Modules have not yet energized their outputs. To activate outputs and to set the Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 37: Transfer Between Active And Standby Modules

    Standby I/O Module into the Standby state. The Active Module is then placed in the Maintain state (which suspends field loop testing), and any Module-specific changeover data is transferred. The educated light flashes amber before the Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 38 Module Removal switches on the currently Active Module and pressing the reset push button on the TMR Processor. This forces the changeover to proceed even if the new Active Module is not fault free. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 39: Specifications

    250 Vrms Mains circuit, OVC II up to 300V. Exposure to voltages at these levels shall be temporally constrained consistent with the system MTTR. Tolerance is ±5 mA up to 0.9 A, thereafter is ±5%. Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 40 Environmental Specifications See Trusted 8000 Series International Safety and Environmental Approvals, publication ICSTT-TD003 Dimensions Height 266 mm (10.5 in) Width 31 mm (1.2 in) Depth 303 mm (12.0 in) Weight 1.3 kg (2.7 lb) Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 41 PD-T8461 Issue 15, January 2019 Change Updated Specifications section and main text to a more consistent format. Updated Front Panel section to updated product design. Updated to display Rockwell Automation publication numbers. Added trademarks statement. PD-T8461 Issue 14, June 2016 Change...
  • Page 42 Appendix A History of Changes PD-T8461 Issue 11, December 2006 Change Weights & Dims PD-T8461 Issue 10, August 2006 Change Channel States PD-T8461 Issue 9, August 2005 Change Format / Text editing Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021...
  • Page 43 At the end of life, this equipment should be collected separately from any unsorted municipal waste. Rockwell Automation maintains current product environmental information on its website at rok.auto/pec. Allen-Bradley, expanding human possibility, Rockwell Automation, TechConnect, and Trusted are trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of ODVA, Inc.