2.1.5 Acceptance and unpacking
Notes for installers
 When units are delivered check whether any damage occurred during shipment. If there is damage to the surface
or outside of a unit, submit a written report to the shipping company.
 Check that the model, specifications and quantity of the units delivered are as ordered.
 Check that all accessories ordered have been included. Retain the Owner's Manual for future reference.
2.1.6 Hoisting
Notes for installers
 Do not remove any packaging before hoisting. If units are not packaged or if the packaging is damaged, use
suitable boards or packing material to protect the units.
 Hoist one unit at a time, using two ropes to ensure stability.
 Keep units upright during hoisting, ensuring that the angle to the vertical does not exceed 30°.
2.2 Mode Selection Box
2.2.1 Placement considerations
Placement of indoor units should take account of the following considerations:
 To prevent the refrigerant noise from disturbing the people in the room, keep at least 5 m of piping between the
occupied room and the MS box.
 If there is no false ceiling in the room, please add sound insulation around the piping between the MS box and the
indoor unit, or keep a much longer distance between the MS box and occupied room.
 To prevent excessive noise or vibration during operation, suspension rods or other weight-bearing fixings should
typically be able to bear twice the unit's weight.
 Sufficient space for drain piping and for access during servicing and maintenance should be allowed.
2.2.2 Spacing
MS box must be spaced such that servicing and maintenance should be allowed. Figures 3-2.8 to 3-2.9 show spacing
requirements for MS box.
124