Table 2-7.1: Outdoor unit electrical characteristics
Model
Capacity
Modules
8HP
10HP
12HP
14HP
16HP
18HP
20HP
22HP
10HP
12HP
24HP
10HP
14HP
26HP
12HP
14HP
28HP
12HP
16HP
30HP
12HP
18HP
32HP
16HP
16HP
34HP
16HP
18HP
16HP
36HP
18HP
18HP
16HP
16HP
38HP
18HP
20HP
16HP
40HP
20HP
20HP
42HP
12HP
14HP
44HP
12HP
16HP
46HP
14HP
16HP
48HP
16HP
16HP
50HP
16HP
16HP
52HP
16HP
18HP
54HP
18HP
18HP
56HP
18HP
18HP
58HP
18HP
20HP
60HP
20HP
20HP
Abbreviations:
MCA: Minimum Circuit Amps; TOCA: Total Over-current Amps; MFA: Maximum Fuse Amps; MSC: Maximum Starting Current (A); RLA: Rated Load Amps; FLA: Full
Load Amps
Notes:
1. Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage
variation between phases is 2%.
2. Select wire size based on the value of MCA.
3. TOCA indicates the total overcurrent amps value of each OC set.
4. MFA is used to select overcurrent circuit breakers and residual-current circuit breakers.
5. MSC indicates the maximum current on compressor start-up in amps.
6. RLA is based on the following conditions: indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB.