Midea V6R Series Manual page 128

Commercial air conditioners
Hide thumbs Also See for V6R Series:
Table of Contents

Advertisement

V6R Series System Commissioning Report – Sheet D
Project name and location
DSP1
Parameters displayed on DSP2
content
0.--
Unit address
1.--
Single module capacity
2.--
Number of outdoor units
3.--
Number of indoor units as set on PCB
4.--
Total capacity of outdoor unit
5.--
Single module compressor frequency
6.--
System compressor frequency
7.--
System operating mode
8.--
Fan A speed index
9.--
Fan B speed index
10.--
Indoor heat exchanger pipe (T2) temperature (°C)
11.--
Indoor heat exchanger pipe (T2B) temperature (°C)
12.--
Main heat exchanger pipe (T3) temperature (°C)
13.--
Outdoor ambient (T4) temperature (°C)
14.--
Outdoor liquid pipe (T5) temperature (°C)
15.--
Plate heat exchanger cooling refrigerant inlet (T6A) temperature (°C)
Plate heat exchanger cooling refrigerant outlet (T6B) temperature
16.--
(°C)
17.--
Inverter compressor discharge (T7C1) temperature (°C)
18.--
Outdoor heat exchanger gas pipe (T8) temperature (°C)
19.--
Compressor inverter module internal (Ntc) temperature (°C)
20.--
Inverter module heatsink (T9)temperature (°C)
21.--
Outdoor heat exchanger liquid pipe (TL) temperature (°C)
22.--
Compressor suction (T7) temperature (°C)
23.--
Discharge superheat degree (°C)
24.--
Primary current (A)
25.--
EXVA position
26.--
EXVC position
27.--
Compressor discharge pressure (MPa)
28.--
Compressor suction pressure (MPa)
29.--
Number of indoor units currently in communication with master unit
30.--
Number of indoor units currently operating
31.--
Heat exchanger status
System startup status
32.--
33.--
Silent setting
System name
Remarks
Master unit: 0; slave units: 1, 2
8-20HP
Displayed on master unit PCB only
Displayed on master unit PCB only
Only available for master unit, displayed
on slave units has no sense
Displayed on master unit PCB only
Actual value = value displayed × 10
0: off; 2: cooling; 3: heating; 4: main
heating; 5: main cooling.
Refer to Note 1
Refer to Note 1
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed × 24
Actual value = value displayed × 4
Actual value = value displayed/10
Actual value = value displayed/100
Displayed on master unit PCB only
Displayed on master unit PCB only
0-OFF; 1-Condenser; 2-Condenser (Not
used); 3-Evaporator; 4-Evaporator (Not
used)
2~4-Startup control; 6-PI control;
Refer to Note 2
Table continued on next page ...
V6R VRF 50/60Hz
Observed values
Cooling
Heating
mode
mode
183