Medical Gas Central Alarm - Medipoint 125 Digital Alarm
present. Typically as per figure 35. Also see table 6 in
section 5 "Operation of the Medipoint 125 Digital alarm"
for troubleshooting.
Confirm for all alarm panels connected to the system.
4.4.2
Fault conditions.
Set the gas service to introduce the 1st alarm condition.
Check the following:
• Check the correct gas legend
• Check the correct location text (if used)
• Ensure that the correct alarm light is illuminates,
• Check that the status bar is the correct colour
• Check the gas service legends are correct and in
accordance with the specification.
• Confirm that the audible alarm is sounding.
This check must be carried out on all panels displaying
that particular gas service.
See table 5 for example, table 7 in section 6 for faull list
of standard equipment and table 6 "Operation of the
Medipoint 125 Digital alarm" for troubleshooting. See
table 2 section 1.8 for full list of standard gas service
fault legends.
Check that the MUTE switch operates satisfactorily.
Press
, the audible alarm will be silenced and the
mute icon will show on screen in yellow
37.
TABLE 5: GAS SERVICE BADGE STATUS, EXAMPLE SHOWING OXYGEN MANIFOLD.
Status Details
Gas type legend & could ID bar
Normal status - Green (normal), blank during fault
Fault status 1 - Blank (normal), Yellow flashing (fault)
Fault status 2 - Blank (normal), Yellow flashing (fault)
Fault status 3 - Blank (normal), Yellow flashing (fault)
Fault status 4 - Blank (normal), Red flashing (fault)
4233500107.03
. See figure
Location
Figure 36 - Example, muted gas 1 low pressure.
4.4.3
Repeat for all gas service inputs.
Repeat sections 4.4.1 through to 4.4.2 for all gas service
4.5
Checking the SYSTEM ALARM
indication.
The procedure for checking that the SYSTEM ALARM
circuits are operating correctly is as follows:-
4.5.1
Electrical power supply. Switch OFF.
Indications. Check.
Check that POWER ON LED is extinguished and SYSTEM
ALARM LED is illuminated (flashing) accompanied by an
audible warning. See figure 37.