Example Of Field Drain Attachment (Not Allowed) - Carrier 59TP6B Installation, Start-Up, Operating And Service And Maintenance Instructions

Two-stage variable speed ecm multipoise condensing gas furnace
Table of Contents

Advertisement

with local building codes. A factory- -supplied 1/2- -in.
CPVC to 3/4- -in. PVC adapter is supplied in the loose parts
bag for use as required.
8. Install the adapter or connect the 1/2- -in. CPVC pipe by
sliding a spring clamp over the open end of the elbow or
grommet on the outside the furnace casing.
9. Open the spring clamp and insert the long end of the
adapter or the 1/2- -in. CPVC pipe into the outlet stub on the
drain tube.
Evaporator Coil
+
+
+
Condensing
Furnace
+
+
+
Blower
-
- -
-
+ = Positive pressure
< + = Pressure lower than areas with +
− = Negative pressure
Evaporator Coil
+ + +
Condensing
Furnace
+
+
+
Blower
-
- -
-
Open
standpipe
3/4" PVC
+
+
+
+
3/4
+
3/4" PVC
3/4
+
3/4
1/2" CPVC or larger*
+
< +
< +
< +
3/4
-
1/2
+
-
1/2
+
3/4
Fig. 13 - - Example of Field Drain Attachment (Not Allowed)
10. Connect additional condensate piping to a code- -approved
drain, or to a condensate pump approved for use with acidic
furnace condensate and compatible with mineral and
vegetable oils, such as canola oil.
Allow at least 1/4-in. per foot (20 mm per meter) of slope down
and away from the furnace in horizontal sections of drain line.
+ = Positive pressure
< + = Pressure lower than areas with +
+
+
+
− = Negative pressure
+
Blower creates positive pressure.
Positive pressure extends into coil
+
condensate drain (no trap).
< +
< +
< +
Furnace condensate does not flow
consistently when drain is at positive
-
+
pressure.
+
-
+
+
Evaporator Coil
+
+
+
Condensing
Furnace
+
+
+
Blower
-
- -
-
+ = Positive pressure
< + = Pressure lower than areas with +
− = Negative pressure
18
3/4" PVC
+
+
+
3/4
+
3/4" PVC
3/4
+
+
3/4
1/2" CPVC or larger*
+
+
< +
3/4
< +
< +
+
+
-
+
+
3/4
-
+
+
+
+
3/4
A14532