equipment does not stage down due to airflow, but the system may stage
down due to high static pressure.
CFM associated for each limit is shown on the screen. Compare this
value with the equipment's low stage CFM value to ensure that
equipment will run for each zone. Assessed airflow is determined as
described in DUCT ASSESSMENT.
After the selections are made, touch SAVE.
• Touch the zone name that you wish to change
• Select the zone to adjust airflow: Low, Med-Low, Medium,
Med-High, High, or No Limit. Default = High

6.3.8.4. Duct Assessment Time

NOTE: The daily duct assessment will occur even if static pressure
monitoring is disabled. This is done to ensure that the system will
continue to provide proper airflow for all installed equipment, since duct
system changes may occur at any time, such as opened or closed
registers.
This option allows the installer to select the time in which the duct
assessment will be performed. After the selection is made, touch SAVE.
• Duct Assessment Time: Selectable between 12 AM and 11PM.
Default = 1 PM

6.3.9. Accessories

First touch SETUP, then touch ACCESSORIES to set up the parameters
for the accessories installed with the system.

6.3.9.1. Filter

NOTE: The daily duct assessment will occur even if static pressure
monitoring is disabled. This is done to ensure that the system will
continue to provide proper airflow for all installed equipment, since duct
53