Electrical Wiring - Valor 1500KN Installation Manual

Direct vent zero clearance gas fireplace
Hide thumbs Also See for 1500KN:
Table of Contents

Advertisement

Installation
Install Electrical Wiring (if required)
This section provides information to install the elec-
tric pre-wiring required for use with the optional
1595CFKV2 Circulating Fan Kit and/or the GV60WIFI WiFi
Kit.
All wiring must be done by a qualifi ed electrician in
accordance with local codes or, in the absence of local
codes, with the National Electrical Code, ANSI/NFPA 70 or
the Canadian Electrical Code, CSA C22.1.
Electrical Requirements
1595CFK—120 VAC, 60 Hz, less than 1 amp
GV60WIFI—6 VDC (from receiver), less than 1 amp
General Requirements
Both optional 1595CFK and GV60WIFI kits require a
GV60VM power supply (known as a V-Module), which
includes a three-prong grounded plug to plug into a
grounded receptacle installed within the fi replace en-
closure by a qualifi ed electrician.
The receptacle, housing, and strain relief are supplied
and installed as part of the fi replace.
Notes
• We recommend connecting the electrical box even if
the optional accessories have not been purchased. It
is much easier to wire before wall fi nish is applied.
• Wiring within the receptacle enclosure must have a
minimum 90°C temperature rating.
• Wire nuts not included.
Installation
1. Locate the electrical housing. It is behind the front
panel of the fi replace in the bottom right corner.
Inner
Cover
Receptacle
Grounding
Stud
2. Remove the inner cover (2 screws).
3. Pull the inner cover and receptacle (attached) out of
the fi replace.

Electrical Wiring

Strain
Relief
Outer
Cover
35