Venting
Installation Into Existing Fireplace Cavity
Co-linear portion of vent system may only be installed
within a solid-fuel burning fi replace and chimney.
The appliance must not be connected to a chimney fl ue
serving a separate solid-fuel burning appliance.
Requires the Valor Co-Axial to Co-Linear appliance
Adapter 1156CLA, two lengths of 2-ply 3" dia. fl exible
chimney liner approved for venting gas appliances, a
co-linear termination kit and fl ashing or a co-linear to
co-axial adapter and either a high wind vertical vent
terminal cap or a low profi le vertical termination.
Firebox zero clearance standoff s supplied with the heater
are not required for this application.
Rules for Co-Linear Venting
1156CLA Co-Linear Vent Adapter
FRONT
11-11/16"
9-3/8"
• Maximum 40 feet vertical pipe
• Minimum 10 feet vertical
• Maximum off set 8 feet with liners at minimum
45 degrees from horizontal plane
• Restrictor: Not required when using co-linear venting.
Installation
For installation of the adapter to the appliance, see the
instructions supplied with the 1156CLA.
Note: Co-linear fl exible aluminum venting should be
professionally inspected periodically for corrosion
and damage and replaced when necessary. If the
installation does not allow for future inspection or
replacement of the fl exible aluminum venting, then
stainless steel vent liners should be used.
26
REAR
3" exhaust
collar
4"
1-1/2"
Co-Linear Conversion
2 x 3"
liners
Co-linear
adapter
3" min.
bend radius
Any fi nishes
applied
around the
fi replace
must be non-
combustible
Co-Linear installation into existing F/P
42"
3" intake
32-3/8"
18"
Approved co-linear
termination or approved
co-linear adapter
and approved
Flashing
co-axial
termination
2 x 3"
liners
1156
Co-linear
adapter
Engine
8-5/8"
3" exhaust collar
on the centerline