Pilz PMI m309 diag Operating Manual
Pilz PMI m309 diag Operating Manual

Pilz PMI m309 diag Operating Manual

Operator terminals

Advertisement

Quick Links

PMI m309 diag
Operator terminals
Operating manual – No. 21870-EN-02

Advertisement

Table of Contents
loading

Summary of Contents for Pilz PMI m309 diag

  • Page 1 PMI m309 diag Operator terminals Operating manual – No. 21870-EN-02...
  • Page 2 This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
  • Page 3: Table Of Contents

    Display Interfaces Range Safety Intended use Safety regulations Unit-specific safety regulations Unit description Front view Side view Interfaces USB port Installation and wiring Safety Installation site and unit surroundings Nominal dimensions Installing the unit Installation PMI m309 diag operating manual...
  • Page 4 PNOZmulti/PSS (Serial) PNOZmulti/PSS (TCP) Enter PMI’s IP address Save diagnostic project (Backup) Select diagnostic language (Language) Backup and Restore 6-10 Password Settings 6-11 System 6-12 Care and maintenance Cleaning the touchscreen Protective membranes Appendix Technical details PMI m309 diag operating manual...
  • Page 5: Introduction

    In this manual the unit is called PMI. The documentation comprises: • The hardware description for the PMI m309 diag • A description of the setup and configuration required for connection to the PVIS OPC Server...
  • Page 6 4 Unit description Introduces the PMI m309 diag in short, simplified form. 5 Installation and wiring This chapter describes how to install and wire the PMI m309 diag. 6 Commissioning This chapter describes the setup and the connection to the OPC Server.
  • Page 7: Definition Of Symbols

    This describes a situation in which the unit(s) could be damaged and also provides information on preventive measures that can be taken. INFORMATION This gives advice on applications and provides information on special features, as well as highlighting areas within the text that are of particular importance. PMI m309 diag operating manual...
  • Page 8 Introduction Notes PMI m309 diag operating manual...
  • Page 9: Overview

    When installed properly, the front of the unit meets protection type IP65. Components Display • PMI m309 diag: 3.5" (89 mm), 320 x 240 pixels and 32 768 colours Interfaces The operator terminal has: • Two serial RS 232 interfaces; one of the interfaces is switchable (RS 232/422/485).
  • Page 10: Range

    Overview Range • Operator terminal • 4 PMI retaining clamps 4 raised head screws (M4) • Plug for supply voltage • Documentation PMI m309 diag operating manual...
  • Page 11: Safety

    Safety Intended use The diagnostic terminal PMI m309 diag is used for diagnostics on PVIS-compatible devices. PVIS-compatible devices are: • Programmable safety and control systems - (PSS/SafetyBUS p) 3rd generation with an FS operating system version >= 53 • PNOZmulti safety relays: - PNOZ m0p from Version 2.0...
  • Page 12: Safety Regulations

    • Unauthorised modifications were carried out • The unit was used outside the technical specifications • The unit was opened or unauthorised repairs were carried out • Operating personnel were not suitably trained or adequately instructed PMI m309 diag operating manual...
  • Page 13: Unit-Specific Safety Regulations

    • Installation site - Do not position PMI m309 diag close to flammable materials. - When installing the unit within a control cabinet, you must ensure the unit’s venting slots are not obstructed, otherwise the unit could be...
  • Page 14 The touchscreen interface is not abrasion-resistant; if it is dirty, please clean with care and do not apply heavy pressure. Further information on care and maintenance of the touchscreen can be found in chapter 7. PMI m309 diag operating manual...
  • Page 15: Unit Description

    Unit description Front view Fig. 4-1: Front view F1 ... F4 (function keys) Touchscreen (see "Technical details") ESC, Enter, Cursor Up, Cursor Down PMI m309 diag operating manual...
  • Page 16: Side View

    Unit description Side view Fig. 4-2: Side view LINE OUT audio interface USB-Slave USB-Host 2 USB-Host 1 COM2 (RS-232/422/485 switchable) serial interface COM1 (RS-232) serial interface Earthing +24 VDC supply voltage Ethernet interface (100 BaseTX) PMI m309 diag operating manual...
  • Page 17: Interfaces

    The USB port is a standard interface, which is unsuitable for continuous duty in an industrial environment due to its reduced noise immunity. For this reason you should limit the time you spend using the USB port to data transfer and PMI diagnostics. PMI m309 diag operating manual...
  • Page 18 Unit description Notes PMI m309 diag operating manual...
  • Page 19: Installation And Wiring

    • Ensure the maximum permissible ambient and operating temperatures are not exceeded. • Ensure that neither liquids nor objects can enter the unit at any time. • Do not position the unit close to flammable materials. PMI m309 diag operating manual...
  • Page 20: Nominal Dimensions

    66 (2.598") t*/mm 52 + 28 (2.047" + 1.102") b3/mm 138 + 1 (5.433" + 0.039") h4/mm 68 + 0,7 (2.677" + 0.027") h*/t* Nominal dimensions without connectors NOTE: Allow extra for hardware connections! PMI m309 diag operating manual...
  • Page 21: Installing The Unit

    - the fixing screws are sufficiently tightened. - the gasket is not damaged. - the wall thickness is at least 2.5 mm. • Protect the unit from falling by ensuring that the fixing screws are sufficiently tightened PMI m309 diag operating manual...
  • Page 22: Installation

    Installation and wiring Installing The PMI 309 fastening kit consists of: Raised head screw (M4) Retaining clip Fig. 5-2: Installing NOTICE The torque setting for the fixing screws may not exceed 0.25 Nm. PMI m309 diag operating manual...
  • Page 23: Connecting The Unit

    • Screened data lines also must always be laid in a different cable duct than the one used for the main power lines. • Power lines should be as short as possible. • Power lines should be twisted pair cables. PMI m309 diag operating manual...
  • Page 24: Earth Connector

    • The connection between the bus bar and the control cabinet/unit must be short and with low impedance. • Fasten the braided screening to the screen bar over as large a surface area as possible (e.g. with metal hose clips or polyurethane (PU) cable clips). PMI m309 diag operating manual...
  • Page 25: Measures To Protect Against Interference Voltages

    1: Earth star point of 24 V DC unit or control cabinet 2: Earth bus bar 3: Supply voltage 4: Earthing terminal (electronic) 5: Earthing bolt (housing) 6: Data line screening Fig. 5-5: Connection example PMI m309 diag operating manual...
  • Page 26 Installation and wiring Notes PMI m309 diag operating manual...
  • Page 27: Commissioning

    "PMIStart.cmd" script file will be run. "PMIStart.cmd" is a batch file which is processed step by step. NOTICE The settings in the PMI configuration must only be changed via SETUP , otherwise the changes will not be applied to the active application. Fig. 6-1: Setup activation PMI m309 diag operating manual...
  • Page 28: Control Panel

    Special features and device-specific settings are described in the following. Fig. 6-2: Systemsteuerung Default diagnostic setting The PMI is supplied with a default diagnostic configuration and a default PMI configuration, so it can immediately be used for device diagnostics (display of system messages). PMI m309 diag operating manual...
  • Page 29: Pvis Expanded Diagnostics

    PVIS expanded diagnostics The diagnostic terminal PMI m309 diag is used for diagnostics on PVIS-compatible devices. PVIS-compatible devices are: • Programmable safety and control systems - (PSS/SafetyBUS p) 3rd generation with an FS operating system version >= 53 • PNOZmulti safety relays: - PNOZ m0p from Version 2.0...
  • Page 30: Select Device/Project (Restore)

    Under the Restore tab, select the device on which diagnostics are to be run. The following devices are available for selection: • PNOZmulti • PSS INFORMATION The default setting is PNOZmulti. Press Install . A prompt will appear before your selection is saved. Fig. 6-3: Restore PMI m309 diag operating manual...
  • Page 31: Configure Connection (Connection Settings)

    PNOZmulti/PSS (Serial) Select the interface ( Port ) under the Connection Settings tab. • COM1 • COM2 Press Set Connection . A prompt will appear before your selection is saved. Fig. 6-4: Connection Settings PNOZmulti/PSS (Serial) PMI m309 diag operating manual...
  • Page 32: Pnozmulti/Pss (Tcp)

    Select the interface ( Port ) under the Connection Settings tab: • TCP Enter the IP address of the converter/PSS. Default setting Port-No : 1025 Press Set Connection . A prompt will appear before your selection is saved. Fig. 6-4: Connection Settings PNOZmulti/PSS (TCP) PMI m309 diag operating manual...
  • Page 33: Enter Pmi's Ip Address

    Proceed as follows: • Under Control Panel, activate the applet Network and Dial-up Connections . A window will open. • Activate the applet ONBOARD ETHERNET #1 . • Enter the IP address of the PMI. PMI m309 diag operating manual...
  • Page 34: Save Diagnostic Project (Backup)

    Backup name: Here you should enter the project name. Backup target folder: Here you should select the target directory. Workdir: Working directory of the current project. Press Pack . The diagnostic project is saved as a “zip file”. Fig. 6-5: Backup PMI m309 diag operating manual...
  • Page 35: Select Diagnostic Language (Language)

    You can change the language setting online at any time. Press Set . A prompt will appear before your language selection is saved. Fig. 6-6: Language Backup and Restore Progam which you can use to save and restore an entire directory structure. PMI m309 diag operating manual...
  • Page 36 Control Panel opens. Timeout If an incorrect password is entered three times or no valid password is entered within the selected time, then the Control Panel is closed. 6-10 PMI m309 diag operating manual...
  • Page 37 Remove "Control Panel Applets" from the password protected area. This area is not protected with a password. INFORMATION Add Password Properties to the password protected area, as otherwise the entered password is not protected and is open to being changed. PMI m309 diag operating manual 6-11...
  • Page 38: System

    Adjust settings to match PMI 2xx : If you press this button, then all of the settings (COM interface etc.) of the predecessor type PMI 2xx are transferred to PMI. 6-12 PMI m309 diag operating manual...
  • Page 39: Care And Maintenance

    The protective membrane can be removed at any time as required - with- out leaving any traces of adhesive on the touchscreen. NOTICE Never use a sharp or pointed object (like a knife) to remove the protective membrane. This could cause damage to the touchscreen. PMI m309 diag operating manual...
  • Page 40 Care and maintenance Notes PMI m309 diag operating manual...
  • Page 41: Appendix

    • 64 MByte/128 MByte (optional) SDRAM • 32 KByte NVRAM battery-buffered Realtime clock Battery-buffered realtime clock Environmental data Noise immunity EN 61000-6-2; Noise emission EN 61000-6-4 Protection type (EN 60529 + A1) Front: IP65, back: IP20 PMI m309 diag operating manual...
  • Page 42 Frequency: 10 ... 150 Hz, constant 1 g Shock (EN 60068-2-27) 15g, 11 ms Mechanical data Dimensions (H x W x D) 87 x 157 x 52 mm Weight 420 g The standards current on 2007-01 apply. PMI m309 diag operating manual...
  • Page 43 +49 711 3409-444 support@pilz.com Please refer to our homepage for further details or contact our headquarters. Pilz GmbH & Co. KG Felix-Wankel-Straße 2 73760 Ostfi ldern, Germany Telephone: +49 711 3409-0 Telefax: +49 711 3409-133 E-Mail: pilz.gmbh@pilz.de...