6

Oil Piping

A. GENERAL.
1. Use flexible oil line(s) so that burner can be
removed without disconnecting the oil supply.
2. A supply line fuel oil filter is recommended as a
minimum for all firing rates but a pleated paper
fuel oil filter is recommended for the lowest
firing rate application to prevent nozzle fouling.
3. Use Flared fittings only. DO NOT use
compression fittings.
4. Use of a high efficiency micron filter (Garber or
equivalent) in addition to conventional filter is
highly recommended.
20
B. SINGLE-PIPE OIL LINES.
Figure 6-1: Single-Pipe Installation
Installation & Service Manual
AP-U
1. Standard burners are provided with single-
stage 3450 rpm fuel units with the bypass plug
removed for single-pipe installations.
2. The single-stage fuel unit may be installed
single-pipe with gravity feed or lift. Maximum
allowable lift is 8 feet. See Figure 6-1.
NOTICE: Oil piping must be absolutely airtight or
leaks or loss of prime may result. Bleed line and
fuel unit completely.