Heating System Piping - New Yorker GHE2-080 Installation, Operating And Service Instructions

Table of Contents

Advertisement

10

Heating System Piping

General System Piping Precautions
!
WARNING
Asphyxiation Hazard.
Failure to properly pipe boiler could cause
improper operation and damage to boiler or
building resulting in severe personal injury,
death or substantial property damage.
Protect gas ignition system components from
water (dripping, spraying, rain, etc.) during
boiler operation and service (circulator
replacement, condensate trap cleaning, control
replacement etc).
Oxygen contamination of boiler water will cause
corrosion of iron and steel boiler components
and could lead to premature boiler failure.
Warranty does not cover problems caused by
oxygen contamination of boiler water or scale
(lime) build-up caused by frequent addition of
water.
Maintain clearances to system piping per
Figure 5-1.
!
CAUTION
Toxic Material.
The heat transfer medium must be water or
other nontoxic fluid having a toxicity rating or
Class of 1, as listed in Clinical Toxicology of
Commercial Products, 5th edition.
Standard Piping Components
1. Safety relief valve (required).
A. Shipped loose in parts carton (30 psig [207
kPa]).
36
GHE II
Installation, Operating & Service Instructions
B. Pipe outlet of safety relief valve to location
where water or steam will not create a
hazard or cause property damage if valve
opens. (The end of discharge pipe must
terminate in unthreaded pipe.)
C. If safety relief valve discharge is not piped to
drain, it must terminate within 6 in. (150 mm)
of floor.
D. Do not route discharge piping through an
area that is prone to freezing temperature.
E. Termination of safety relief valve must be in an
area where it is not likely to become plugged
by debris.
F.
If replaced, replacement must have a setting
less than or equal to maximum allowable
working pressure (MAWP) shown on ASME
data plate located on left side of heat
exchanger (50 psig [345 kPa]).
Burn Hazard.
Safety relief valve discharge piping must
be piped near floor to eliminate potential
of severe burns. Do not pipe in any shut-off
valves between:
1. Safety relief valve and boiler.
2. Safety relief valve and discharge.
Union may be installed in safety relief valve
piping.
2. Pump (required)
Boiler loop pump is supplied with this boiler and
sized for near boiler piping equivalent length of 50
ft. See Table 10-1 for flow range through boiler. At
least one additional pump is required on system
side.
!
WARNING
110330-03 - 2/23