NOTE:
*1. If the field-supplied snow protection hood or the air flow deflector duct is adopted, the space of minimum 50mm is required.
*2. Partly open a wall if the unit is surrounded by walls at four sides.
3. Keep the top of the outdoor unit without any obstacle to prevent short circuit due to inlet air and outlet air of each outdoor unit.
4. The above chart provides sufficient operation and maintenance space for outdoor unit under standard operation conditions.
(operating mode: cooling, ambient temperature: 35 degrees) If the outdoor unit ambient temperature is higher, and there is a outlet
air short circuit, adjust the installation size depending on the actual installation conditions, and the calculation of outdoor unit return
airflow.
5. When multiple outdoor units are installed in the same direction, you can install a maximum of six outdoor units. The minimum
distance between two adjacent outdoor units should be at least 1m.

5.4 Foundation

● Concrete Foundation:
(1) The foundation should be 150 mm higher than the ground.
(2) Set the drain ditch around the base to ensure smooth drainage.
* Please set the concrete base as shown below:
* Do not setup the concrete foundation as shown below. Otherwise, the foot of the machine may
be deformed:
1 Group (Max. 6 Outdoor Units)
More than 100
Foundation
Min. 1m
Refrigerant pipe
More than 100
Rubber
Drainage ditch
cushion
Correct
Incorrect
The front side
of the unit
Foundation
16
(mm)
Hole for foot bolt,
Dia.100xdepth150
Drainage ditch
width100xdepth20
The front side
of the unit
Feet
Feet