Siemens Climatix HMI-TM Basic Documentation page 27

Table of Contents

Advertisement

Key definition
Siemens
Building technologies
2. Define the sub page in target column.
a. Target Page No. of "Enumeration scheduler" is "64900..64909".
Object type must be "0x220B". It is connected to a Multistate
Object (e.g. StptMultistate or any other Multistate-Object).
b. Target Page No. of "Set point scheduler" is "64910..64919". Object
type must be "0x220A". It is connected to a Value Object (e.g.
StptValue or any other Analog-Object).
HMI DM/TM with BSP 10.xx or above can still display text time scheduler. Set up
target page for text time scheduler out of above ranges. Those page ranges are
dedicated for graphical time scheduler function with HMI BSP 10.xx or above.
3. Create a time scheduler function in SAPRO as follows:
4. The screen will be shown as follows:
Key
Action
ESC
Press
UP
Press
DOWN
Press
ENTER
Press
INFO
Long press (3 sec.)
Climatix HMI-TM
3BFunctions and operations
Description
To exit from the time scheduler page
-
To adjust date and time
-
To change the enumeration or set point
To confirm the selection
To delete a time scheduler entry
27 / 38
CB1P3917en02
2015-07-02