Phocos Any-Grid Series Firmware Upgrade Manual page 6

Hide thumbs Also See for Any-Grid Series:
Table of Contents

Advertisement

7.
Once the progress reaches 100%, the Any-Grid unit will restart automatically. The Upgrader software will
show "Verify flash data ok!" and "COM was closed" messages in the log area. You may now exit the Upgrader
software.
8.
The Any-Grid may be disconnected from its power source 2 minutes after its automatic restart is complete.
Alternatively, manually turn off the unit (load ON/OFF switch on display unit set to OFF). The unit will turn off
after a few seconds. Leave it off for at least a minute (ensure the display is off ). You may now reconnect the
battery or AC input, whichever was disconnected during the procedure (if any). Turn on the unit again (load
ON/OFF switch on display unit set to ON). Then continue to connect the PV array and loads as required.
9.
The "Display Unit" upgrade procedure is complete. You can check the new version number as described in
the chapter "Introduction" of this document.