Unit installation

6.3 Mounting the indoor unit

In this chapter

6.3.1 To install the mounting plate

122
d
a
e
56.5
a Recommended mounting plate fixing spots
b Pocket for the pipe port cover
c Tabs for placing a spirit level
d Through-the-wall hole Ø65 mm
e Drain hose position

6.3.2 To drill a wall hole

Installer reference guide
24
6.3.1

To install the mounting plate.................................................................................................................................

6.3.2

To drill a wall hole ..................................................................................................................................................

6.3.3
To remove the pipe port cover ..............................................................................................................................
1 Install the mounting plate temporarily.
2 Level the mounting plate.
3 Mark the centres of the drilling points on the wall using a tape measure.
Position the end of tape measure at symbol " ".
4 Finish the installation by securing the mounting plate on the wall using
M4×25L screws (field supply).
INFORMATION
The removed pipe port cover can be kept in the mounting plate pocket.
a
b
PIPING HOLE
PIPING HOLE
CENTER:170mm
CENTER:170mm
TO THE LEFT
TO THE LEFT
f1
A
170
475
CAUTION
For walls containing a metal frame or a metal board, use a wall embedded pipe and
wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
NOTICE
Be sure to seal the gaps around the pipes with sealing material (field supply), in order
to prevent water leakage.
1 Bore a 65  mm large feed-through hole in the wall with a downward slope
towards the outside.
2 Insert a wall embedded pipe into the hole.
a
c
c
h
i
g
60
990
f1 Measure point for piping hole center " " (to left)
f2 Measure point for piping hole center " " (to right)
g Gas pipe end
h Liquid pipe end
i Center of the unit
a
PIPING HOLE
PIPING HOLE
CENTER:170mm
CENTER:170mm
TO THE RIGHT
f2
A
A
a
170
404
FTXP-M + FTXF-D + FTXF-A + ATXF-A
24
24
25
121.5
d
e
56.5
(mm)
Daikin room air conditioner
4P513661-12L – 2021.07