6
|
Unit installation
6.4.1 General guidelines
Installer reference guide
26
▪
Pipe length. Keep drain piping as short as possible.
▪
Pipe size. If drain hose extension or embedded drain piping is required, use
appropriate parts that match the hose front end.
NOTICE
▪
Install the drain hose with a downward slope.
▪
Traps are NOT permitted.
▪
Do NOT put the end of the hose in water.
▪
Drain hose extension. To extend the drain hose, use a field supplied hose with
inner Ø16 mm. Do NOT forget to use a heat insulation tube on the indoor section
of the extension hose.
a
a Drain hose supplied with the indoor unit
b Heat insulation tube (field supply)
c Extension drain hose
▪
Ridgid polyvinyl chloride pipe. When connecting a ridgid polyvinyl chloride pipe
(nominal Ø13 mm) directly to the drain hose as with embedded piping work, use
a field supplied drain socket (nominal Ø13 mm).
a
a Drain hose supplied with the indoor unit
b Drain socket with nominal Ø13 mm (field supply)
c Ridgid polyvinyl chloride pipe (field supply)
▪
Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
1 Insert the drain hose in the drain pipe as shown in the following figure, so it
will NOT be pulled out of the drain pipe.
mm
a
b
c
b
c
FTXP-M + FTXF-D + FTXF-A + ATXF-A
Daikin room air conditioner
4P513661-12L – 2021.07