Unit installation

6.4.1 General guidelines

Installer reference guide
26
Pipe length. Keep drain piping as short as possible.
Pipe size. If drain hose extension or embedded drain piping is required, use
appropriate parts that match the hose front end.
NOTICE
Install the drain hose with a downward slope.
Traps are NOT permitted.
Do NOT put the end of the hose in water.
Drain hose extension. To extend the drain hose, use a field supplied hose with
inner Ø16 mm. Do NOT forget to use a heat insulation tube on the indoor section
of the extension hose.
a
a Drain hose supplied with the indoor unit
b Heat insulation tube (field supply)
c Extension drain hose
Ridgid polyvinyl chloride pipe. When connecting a ridgid polyvinyl chloride pipe
(nominal Ø13 mm) directly to the drain hose as with embedded piping work, use
a field supplied drain socket (nominal Ø13 mm).
a
a Drain hose supplied with the indoor unit
b Drain socket with nominal Ø13 mm (field supply)
c Ridgid polyvinyl chloride pipe (field supply)
Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
1 Insert the drain hose in the drain pipe as shown in the following figure, so it
will NOT be pulled out of the drain pipe.
mm
a
b
c
b
c
FTXP-M + FTXF-D + FTXF-A + ATXF-A
Daikin room air conditioner
4P513661-12L – 2021.07