15.5 Room temperature hysteresis (P.49)
Parameter P.49 can be used to adjust the hysteresis of the room temperature required to reactivate
the demand, i.e. once the desired room temperature has been reached in the room, how much it will
have to fall below that temperature for the heating demand to be reactivated. The appropriate choice
of the value of this parameter will avoid excessive cycling of the activation of the heating demand of
the boiler, optimising its operation. The optimal value will depend on the level of the home's thermal
insulation; the higher the insulation level, the lower the value of parameter P.49 can be. In turn, if the
insulation level is reduced, it is recommended to increase the parameter. This parameter will only be
applied in heating zones where there is a connected room sensor. The selectable range of parameter
P.49 is 0.2 - 5ºC and the factory default value is 0.5ºC.
15.6 Room temperature correction (P.51, P.52, P.53)
Through these parameters it is possible to compensate the temperature measurements differences in
the temperature sensors. Selectable range P.51 (zone 1), P.52 (zone 2) and P.53 (zone 3) is -5,0 -
+5,0 ºC and the default value is 0,0 ºC.