Capacity Tables - Daikin FTV-A Series Engineering Data

Split unit air conditioner wall mounted
Table of Contents

Advertisement

Capacity Tables

Calculation Steps
Interpolation method can be used to get the total
cooling capacity, TC and sensible cooling capacity,
SC and power input, PI at those temperatures which
are not stated out in the table. Extrapolation method
is not allowed to be used.
Example:
Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 37°C DB
Fan Speed: High
1
Step
st
Interpolation of Indoor WB
Find TC, SC & PI
(a) Indoor: 25°C DB, 16°C WB
Outdoor: 35°C DB
(b) Indoor: 25°C DB, 19°C WB
Outdoor: 35°C DB
(c) Indoor: 25°C DB, 16°C WB
Outdoor: 40°C DB
(d) Indoor: 25°C DB, 19°C WB
Outdoor: 40°C DB
Details of Calculation:
1
Step:
st
To obtain the TC, SC & PI for
(a) Indoor Condition: 25°C DB, 16°C WB
Outdoor Condition: 35°C DB
EWB
EDB
24
16
25
27
2
Step
nd
Interpolation of Indoor DB
Find TC, SC & PI
(a) Indoor: 25°C DB, 17°C WB
Outdoor: 35°C DB
(b) Indoor: 25°C DB, 17°C WB
Outdoor: 40°C DB
Outdoor temperature
35°C
TC
SC
PI
1.80
1.71
0.63
x
y
z
1
1
1
1.83
1.83
0.63
Solution:
Based on the Performance Table,
1. Refer to the Indoor DB column,
- 25°C is located between 24°C & 27°C
for 16°C WB.
- 25°C is located between 24°C & 27°C
for 19°C WB.
- Thus, Interpolation needs to be applied.
2. Refer to the Indoor WB column,
- 17°C is located between 16°C & 19°C
for 25°C DB.
- Thus, Interpolation needs to be applied.
3. Refer to the Outdoor DB column,
- 37°C is located between 35°C & 40°C.
- Thus, Interpolation needs to be applied.
3
Step
rd
Interpolation of Outdoor DB
Find TC, SC & PI
(a) Indoor: 25°C DB, 17°C WB
Outdoor: 37°C DB
By Interpolation Method
25°C – 24°C
=
27°C – 24°C
1.83kW – 1.80kW
⇒ x
= 1.81kW
1
Similarly,
y
= 1.75kW
1
z
= 0.63kW
1
Capacity Tables
x
– 1.80kW
1
43