Electric Characteristic - Daikin FTV-A Series Engineering Data

Split unit air conditioner wall mounted
Table of Contents

Advertisement

Electric Characteristic

Unit Combination
Indoor Unit
Outdoor Unit
FTV28A
RV28A
FTV35A
RV35A
FTV50A
RV50A
FTV60A
RV60A
Symbols:
MCA
: Min. circuit amps (A)
MFA
: Max. fuse amps (A)
LRA
: Locked Rotor Ampere (A)
RLA
: Rated loads amps (A)
OFM
: Outdoor fan motor
IFM
: Indoor fan motor
W
: Fan motor rated output (W)
FLA
: Full load amps (A)
Power Supply
Hz
Volts
Voltage Range
50
220
Max. 50Hz 264V
50
230
Min. 50Hz 198V
50
240
50
220
Max. 50Hz 264V
50
230
Min. 50Hz 198V
50
240
50
220
Max. 50Hz 264V
50
230
Min. 50Hz 198V
50
240
50
220
Max. 50Hz 264V
50
230
Min. 50Hz 198V
50
240
COMP
MCA
MFA
LRA
4.70
16.0
16.0
5.96
16.0
30.1
9.19
20.0
38.0
12.4
20.0
52.0
Notes:
1. RLA is based on the following conditions.
Indoor temp. 27°CDB / 19°CWB.
Outdoor temp. 35°CDB.
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
detector capable of handling high harmonics must be used in
order to prevent malfuctioning of the earth leak detector.)
Electric Characteristic
OFM
IFM
RLA
kW
FLA
kW
3.34
0.050
0.22
0.037
4.34
0.051
0.23
0.042
6.74
0.092
0.41
0.044
9.11
0.092
0.41
0.077
FLA
0.20
0.20
0.20
0.36
67