2 Operation

2.1 Flame simulator activation

Warnings:
• Testing using a flame simulator to simulate a fire to the detector may activate
alarms or extinguishing systems in the area unless disabled/inhibited/bypassed.
• All tests should be coordinated, and if needed, disconnect/disable the alarm
and/or the extinguishing systems before the test, and reconnect after the test.
1. Remove simulator from the case and verify the simulator battery is charged.
2. Ensure use of the correct flame simulator model according to the detector type.
3. Make sure you are testing within the specified distance, according to the detector
sensitivity. See Table 1 below.
4. Point the flame simulator at center of detector by aligning the front and back aiming
sights located on the top of the simulator (3).
5. The simulator should be aimed within +/- 30⁰ from the horizontal and vertical center
line axis of the detector.
6. Press the push button (4) to activate, notice the flashing green LED. Wait for the
flame detector to enter into alarm (typically 10 seconds). Go to the next detector
and repeat the test.