FlameSpec Flame Simulator Manual
Note: factory default settings for Detectors sensitivity is Medium
Simulator Kit
Use with
Detector Model
Extreme
Detector
High
Sensitivity
Medium
Setting
Low
3 LED Status, Faults & Warnings
The flame simulator has a tri-color LED which indicates the operational status of the simulator as
described in the table below.
LED Status
Flashing green
Flashing orange
Solid orange
Solid red
Off
Flashing green LED
but simulator fails to
activate detector
alarm
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com
FLS-FSIM-IR3-KIT
FLS-IR3-HD
FLS-IR3
ft. (m)
23.0 (7.0)
16.0 (5.0)
10.0 (3.0)
3.3 (1.0)
Indication
Normal operation
Battery at medium capacity
Unit is in fail mode
No power
No power
Detector is unable to read the
signal from the Simulator
Doc. No. F300V0020.01
FLS-FSIM-IR3-H2-KIT
FLS-IR3-H2-HD
FLS-IR3-H2
ft. (m)
23.0 (7.0)
16.0 (5.0)
10.0 (3.0)
3.3 (1.0)
Action
Ready for use
Charge battery for 3 hours
Return for repair
Recharge/replace the battery
Recharge/replace the battery
1. Check you are within the specified distance
from the detector according to the detector's
sensitivity setting.
2. Check detector is powered and operational.
3. Check simulator window is clean.
4. Check detector window is clean, and not in
fault or indicating 2mA output to the panel
indicating a dirty window.
Note: Any alarm delay set in the detector will
require the simulator to be aimed at the detector
for that period plus up to 10 more seconds.
FLS-FSIM-UV-IR-KIT
FLS-UV-IR-HD
FLS-UV-IR
ft. (m)
21.3 (6.5)
16.0 (5.0)
13.0 (4.0)
3.3 (1.0)
3