Operation; Output Signals; Table 4: Output Signals - FGD FlameSpec IR3-HD User Manual

Table of Contents

Advertisement

FlameSpec IR3-HD User Manual

5 Operation

The FlameSpec-IR3-HD is a triple-IR flame detector that includes a built-in high-definition video camera
module. The video module automatically records video of alarm events, and can provide live video of the
detection zone to a screen in the control room.
The detector is ready for detecting fire approximately 30 seconds after power up. During this startup time the
LED flashes Yellow. If the startup is successful, the indication LED turns to green, the 0-20mA indicates 4mA
and the fault relay is closed. The video module starts operating approximately 2 minutes after power up.
Detector configuration settings can be changed as described in section 3.
To restart the detector, turn off and then turn on the power.

5.1 Output Signals

The detector has the following output signals:
Current output (0–20mA)
Relays (Fault and Alarm)
RS-485
Tri-color LED
0 – 20mA
Fault Relay (NO)
Alarm Relay NO
LED
For more information & Technical support: (+1) 714-671-8500 · support@fg-detection.com
T
ABLE
Startup
Fault
1mA
1mA
Open
Open
Open
Open
Flashing
Flashing
Yellow
Yellow
F101V0020.05
4: O
S
UTPUT
IGNALS
Dirty Window
2mA
Open
Open
Yellow
Normal
Fire Alarm
4mA
20mA
Closed
Closed
Open
Closed
Green
Red